697
Auxiliary Area Allocations by Address
Appendix D
A514
All
Number of
Power Inter-
ruptions
Contains the number of times that
power has been interrupted since the
power was first turned ON. The data
is stored in binary. To reset this
value, overwrite the current value
with 0000.
(This word is not cleared at startup,
but it is cleared when the Memory
Corruption Detected Flag (A395.11)
goes ON.)
0000 to FFFF
hexadecimal
Retained
Retained
Refresh-
ed when
power is
turned
ON.
A395.11
A515 to
A517
All
Operation
Start Time
The time that operation started as a
result of changing the operating
mode to RUN or MONITOR mode is
stored here in BCD.
A515.00 to A515.07: Seconds (00 to
59)
A515.08 to A515.15: Minutes (00 to
59)
A516.00 to A516.07: Hour (00 to 23)
A516.08 to A516.15: Day of month
(01 to 31)
A517.00 to A517.07: Month (01 to
12)
A517.08 to A517.15: Year (00 to 99)
Note
The previous start time is
stored after turning ON the
power supply until operation
is started.
See at left.
Retained
Retained
See at
left.
---
A518 to
A520
All
Operation
End Time
The time that operation stopped as a
result of changing the operating
mode to PROGRAM mode is stored
here in BCD.
A518.00 to A518.07: Seconds (00 to
59)
A518.08 to A518.15: Minutes (01 to
59)
A519.00 to A519.07: Hour (00 to 23)
A519.08 to A519.15: Day of month
(01 to 31)
A520.00 to A520.07: Month (01 to
12)
A520.08 to A520.15: Year (00 to 99)
Note
If an error occurs in operation,
the time of the error will be
stored. If the operating mode
is then changed to PRO-
GRAM mode, the time that
PROGRAM mode was
entered will be stored.
See at left.
Retained
Retained
See at
left.
---
A523
All
Total Power
ON Time
Contains the total time that the PLC
has been ON in 10-hour units. The
data is stored in binary and it is
updated every 10 hours. To reset this
value, overwrite the current value
with 0000.
(This word is not cleared at startup,
but it is cleared to 0000 when the
Memory Corruption Detected Flag
(A395.11) goes ON.)
0000 to FFFF
hexadecimal
Retained
Retained
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...