614
Troubleshooting
Section 11-2
11-2-5 Non-fatal Errors
A non-fatal error has occurred if both the RUN indicator and the ERR/ALM
indicator are lit during operation (i.e., in RUN or MONITOR mode).
■
CPU Unit Indicators
Information on the non-fatal error can be obtained from the Error Tab Page of
the CX-Programmer’s PLC Error Window. Take corrective actions after check-
ing error details using the display messages and the Auxiliary Area Error
Flags and error information.
• Errors are listed in the following table in order, with the most serious ones
first.
• If two or more errors occur at the same time, the most serious error code
will be stored in A400.
Errors Created with for FAL Instructions
A FAL instruction was executed in the program to create a non-fatal error.
■
Reference Information
Flash Memory Errors
■
Reference Information
POWER
Lit
RUN
Lit
ERR/ALM
Flashing
INH
---
BKUP
---
PRPHL
---
POWER
RUN
INH
PRPHL
BKUP
ERR/AL
Probable cause
Possible remedy
The executed FAL number 001 to 511 will
be stored in A360 to A391. The number 4
will be added to the front of 101 to 2FF
(which correspond to executed FAL num-
bers 001 to 511) and the result will be
stored in A400 as error code 4101 to
42FF.
Check the conditions for executing FAL
instructions and remove any causes of
the user-defined error.
Error flag
FAL Error Flag, A402.15
Error code (A400)
4101 to 42FF
Error information
None
Probable cause
Possible remedy
A315.15 will turn ON when writing to the
internal flash memory fails.
Replace the CPU Unit when the internal
flash memory has been written to more
than 100,000 times.
Error flag
Flash Memory Error Flag, A315.15
Other non-fatal flags, A402.00
Error code (A400)
None
Error information
None
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...