Error Classification and Confirmation
Section 11-1
11-1 Error Classification and Confirmation
Error Categories
Errors in CP1L CPU Units can be broadly divided into the following four cate-
gories.
Confirming Errors
There are three sources of information on errors that have occurred.
• CPU Unit indicators
• Auxiliary Area
CPU Unit Indicators
These indicators show the operating status of the CPU Unit.
Note
Do not turn OFF the CPU Unit power supply when this indicator is lit.
Category
Comments
CPU Error
A WDT (watchdog timer) error is generated in the CPU Unit, the
CPU Unit will malfunction, and operation will stop.
CPU Standby
The CPU will go on standby because conditions for stating oper-
ation have not yet been met.
Fatal Error
Operation cannot continue. Operation will stop due to a serious
problem.
Non-fatal Error
A minor problem has occurred. Operation will continue
POWER
RUN
INH
PRPHL
BKUP
ERR/ALM
POWER
(green)
Lit
Power is ON.
Not lit
Power is OFF.
RUN (green)
Lit
The CPU Unit is executing a program in either RUN or
MONITOR mode.
Not lit
Operation is stopped in PROGRAM mode or due to a
fatal error.
ERR/ALM
(red)
Lit
A fatal error or CPU error (WDT error) has occurred.
operation will stop and all outputs will be turned OFF.
Flashing
A non-fatal error has occurred. Operation will continue.
Not lit
Operation is normal.
INH (yellow)
Lit
The Output OFF Bit (A500.15) was turned ON. All out-
puts will be turned OFF.
Not lit
Operation is normal.
PRPHL
(yellow)
Flashing
Communications (either sending or receiving) are in
progress through the peripheral port.
Not lit
Other than the above.
BKUP
(yellow)
(See note.)
Lit
• The user program, parameters, or DM Area
data is being written to or accessed in the
built-in flash memory (backup memory).
• The user program, parameters, DM Area data,
or DM initial values are being written to or
accessed in a Memory Cassette.
• The BKUP indicator also lights while the user
program is being restored when the power
supply is turned ON.
Not lit
Other than the above.
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...