344
Interrupt Functions
Section 6-1
Setting the Input Functions in the PLC Setup
Normally, bits CIO 0.04 to CIO 0.09 are used as normal inputs. When using
these inputs for input interrupts, use the CX-Programmer to change the
input’s setting in the PLC Setup.
Note
*Input interrupts 4 and 5 are not supported by CPU Units with 10 or 14 I/O
Points.
**Input interrupts 2 and 3 are not supported by CPU Units with 10 I/O Points.
Procedure
Input terminal
block
CPU Unit
Input
interrupt
Task
number
Word
Bit
CPU Units with
60 I/O Points
CPU Units with
40 I/O Points
CPU Units with
30 I/O Points
CPU Units with
20 I/O Points
CPU Units with
14 I/O Points
CPU Units with
10 I/O Points
CIO 0 00
Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 Normal input 0 ---
---
01
Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 Normal input 1 ---
---
02
Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 Normal input 2 ---
---
03
Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 Normal input 3 ---
---
04
Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Normal input 4 Input
interrupt 0
Interrupt
task 140
05
Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Normal input 5 Input
interrupt 1
Interrupt
task 141
06
Normal input 6 Normal input 6 Normal input 6 Normal input 6 Normal input 6 ---
Input
interrupt
2**
Interrupt
task
142**
07
Normal input 7 Normal input 7 Normal input 7 Normal input 7 Normal input 7 ---
Input
interrupt
3**
Interrupt
task
143**
08
Normal input 8 Normal input 8 Normal input 8 Normal input 8 ---
---
Input
interrupt
4*
Interrupt
task
144*
09
Normal input 9 Normal input 9 Normal input 9 Normal input 9 ---
---
Input
interrupt
5*
Interrupt
task
145*
10
Normal input
10
Normal input
10
Normal input
10
Normal input
10
---
---
---
---
11
Normal input
11
Normal input
11
Normal input
11
Normal input
11
---
---
---
---
CIO 1 00 to
05
Normal input
12 to 17
Normal input
12 to 17
Normal input
12 to 17
---
---
---
---
---
06 to
11
Normal inputs
18 to 23
Normal inputs
18 to 23
---
---
---
---
---
---
CIO 2 00 to
11
Normal inputs
24 to 35
---
---
---
---
---
---
---
Select the input interrupts.
• Determine the inputs to be used for input
interrupts and corresponding task numbers.
↓
Wire the inputs.
• Wire the inputs.
↓
Set the PLC Setup.
• Use the CX-Programmer to select the inter-
rupt inputs in the PLC Setup.
↓
Write the ladder program.
• Write the programs for the corresponding
interrupt task numbers.
• Use MSKS(690) to specify up-differentiation
or down-differentiation.
• Use MSKS(690) to enable input interrupts (in
direct mode).
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...