665
Appendix D
Auxiliary Area Allocations by Address
Read-only Area (Set by System)
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
A0
---
10-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1 every
10 ms. The value returns to 0000 hex
after reaching FFFF hex
(655,350 ms), and then continues to
be automatically incremented by 1
every 10 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 10 ms units.
---
Retained
Cleared
Every
10 ms after
power is
turned ON
---
A1
---
100-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1 every
100 ms. The value returns to 0000
hex after reaching FFFF hex
(6,553,500 ms), and then continues
to be automatically incremented by 1
every 100 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 100 ms units.
---
Retained
Cleared
Every
100 ms
after power
is turned
ON
---
A20
and
A21
---
Present Value
of Unsigned
Output Value
0
These words contain the present
value of the unsigned output value
(output value = present value of error
counter
×
error counter cycle (s)
×
gain) for inverter positioning 0.
Data range: 0000 0000 to
8000 0000 hex (0 to 2,147,483,648)
The maximum and minimum output
values set for inverter positioning 0 in
the PLC Setup are applied.
A21 contains the leftmost 4 digits
and A20 contains the rightmost 4
digits.
---
---
Cleared
Every error
counter 0
cycle
---
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...