177
High-speed Counters
Section 5-1
5-1-2
High-speed Counter Specifications
Specifications
Item
Specification
Number of high-speed counters
2 (High-speed counters 0 and 1)
4 (High-speed
counters 0 to 3)
Pulse input modes (Selected in the PLC
Setup)
Differential phase
inputs
Up/down inputs
Pulse + direction
inputs
Increment inputs
Input terminal allocation
Phase-A input
Increment pulse
input
Pulse input
Increment pulse
input
Phase-B input
Decrement pulse
input
Direction input
---
Phase-Z input
Reset input
Reset input
Reset input
Input method
Differential phase,
4x
(Fixed)
Two single-phase
inputs
Single-phase
pulse + direction
inputs
Single-phase
input
Response frequency
50 kHz
100 kHz
100 kHz
100 kHz
Counting mode
Linear mode or circular (ring) mode (Select in the PLC Setup.)
Count values
Linear mode: 8000 0000 to 7FFF FFFF hex
Ring mode: 0000 0000 to Ring SV
(The Ring SV (Circular Max. Count) is set in the PLC Setup and the setting
range is 00000001 to FFFFFFFF hex.)
High-speed counter PV storage locations
High-speed counter 0: A271 (leftmost 4 digits) and A270 (rightmost 4 digits)
High-speed counter 1: A273 (leftmost 4 digits) and A272 (rightmost 4 digits)
High-speed counter 2: A317 (leftmost 4 digits) and A316 (rightmost 4 digits)
High-speed counter 3: A319 (leftmost 4 digits) and A318 (rightmost 4 digits)
Target value comparison interrupts or range comparison interrupts can be
executed based on these PVs.
Note
The PVs are refreshed in the overseeing processes at the start of each
cycle. Use PRV(881) to read the most recent PVs.
Data format: 8 digit hexadecimal
Range in linear mode: 8000 0000 to 7FFF FFFF hex
Range in ring mode: 0000 0000 to Ring SV (Circular Max. Count)
Control
method
Target value comparison
Up to 48 target values and corresponding interrupt task numbers can be reg-
istered.
Range comparison
Up to 8 ranges can be registered, with a separate upper limit, lower limit, and
interrupt task number for each range.
Counter reset method
Select one of the following methods in the PLC Setup.
•Phase-Z + Software reset
The counter is reset when the phase-Z input goes ON while the Reset Bit is
ON.
•Software reset
The counter is reset when the Reset Bit goes ON.
(Set the counter reset method in the PLC Setup.)
Note
Operation can be set to stop or continue the comparison operation
when the high-speed counter is reset.
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...