623
Inspections
Section 12-1
Note
The following table shows the allowable voltage fluctuation ranges for source
power supplies.
Tools Required for Inspections
Required Tools
• Phillips screwdrivers
• Voltage tester or digital voltmeter
• Industrial alcohol and clean cotton cloth
Tools Required Occasionally
• Synchroscope
• Oscilloscope with pen plotter
• Thermometer and hygrometer
12-1-2 Unit Replacement Precautions
Check the following when replacing any faulty Unit.
• Do not replace a Unit until the power is turned OFF.
• Check the new Unit to make sure that there are no errors.
• If a faulty Unit is being returned for repair, describe the problem in as
much detail as possible, enclose this description with the Unit, and return
the Unit to your OMRON representative.
• For poor contact, take a clean cotton cloth, soak the cloth in industrial
alcohol, and carefully wipe the contacts clean. Be sure to remove any lint
prior to remounting the Unit.
Note
When replacing a CPU Unit, be sure that not only the user program but also
all other data required for operation is transferred to or set in the new CPU
Unit before starting operation, including DM Area and HR Area settings. If
4
Installation and
wiring
Check that each Unit is con-
nected securely and locked in
place.
No looseness
Press the connectors together
completely and lock them with the
sliders.
Check that the Option Boards
and cable connectors are fully
inserted and locked.
No looseness
Correct any improperly installed
connectors.
Check for loose screws in
external wiring.
No looseness
Tighten loose screws with a Phillips
screwdriver.
Check crimp connectors in
external wiring.
Adequate spacing between
connectors
Check visually and adjust if neces-
sary.
Check for damaged external
wiring cables.
No damage
Check visually and replace cables if
necessary.
5
User-service-
able parts
Check whether the battery
has reached its service life.
CJ1W-BAT01 Battery
Service life expectancy is 5
years at 25
°
C, less at
higher temperatures.
(From 0.75 to 5 years
depending on model,
power supply rate, and
ambient temperature.)
Replace the battery when its ser-
vice life has passed even if a bat-
tery error has not occurred.
CPU Unit
Supply voltage
Allowable voltage range
CP1L-M
@@
D
@
-A
CP1L-L
@@
D
@
-A
100 to 240 V AC
85 to 264 V AC
(+10%/
−
15%)
CP1L-M
@@
D
@
-D
CP1L-L
@@
D
@
-D
24 V DC
20.4 to 26.4 V DC
(+10%/
−
15%)
No.
Item
Inspection
Criteria
Action
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...