553
Ethernet Option Board Function Guide
Section 9-1
9-1-2
Connecting the CX-Programmer to PLCs Online via Ethernet
Connecting within the
Same Segment
Use the UDP/IP version of the FINS communications service (i.e.,
FINS/UDP). FINS/UDP is supported by many OMRON products and is com-
patible with earlier Ethernet Units (CS1W-ETN01/ETN11/ETN21 and CJ1W-
ETN11/ETN21). The CX-Programmer can be connected and used with
FINS/UDP.
Connecting through
Multiple Segments
Use the TCP/IP version of the FINS communications service (i.e., FINS/TCP).
It provides automatic recovery at the TCP/IP layer from communications
errors (such as packet loss) that occur during multilevel routing. For CX-Pro-
grammer, FINS/TCP can be used to directly connect to the PLC online.
Using Media with
Unreliable Connections,
Such as a Wireless LAN
Use the TCP/IP version of the FINS communications service (i.e., FINS/TCP).
It provides automatic recovery at the TCP/IP layer from communications
errors (such as packet loss) resulting from unreliable connections. For CX-
Programmer, FINS/TCP can be used to directly connect to the PLC online.
Connecting from a
Personal Computer with a
Dynamic Private IP
Address
Depending on whether or not the connection will be within the same segment,
either use an IP address conversion method for dynamic IP addresses in the
UDP/IP version of the FINS communications service or use the TCP/IP ver-
sion of the FINS communications service.
It is possible to connect online to a PLC using the CX-Programmer from a
computer serving as a temporarily connected node or a permanent DHCP cli-
ent.
For CX-Programmer, FINS/TCP can be used to directly connect to the PLC
online.
Connecting through multiple segments, such as over the Internet:
Use FINS/TCP.
FINS
Internet
IP router
Firewall
Intranet
(Office floor)
CX-Programmer
FINS
Ethernet
Ethernet
Router
(Production line)
Ethernet
Connecting within the same segment:
Use FINS/UDP.
PLC
PLC
Wireless
FINS
Using media with unreliable
connections, such as wireless
LAN: Use FINS/TCP.
FINS
Connecting from a computer with a dynamic private IP address:
Use FINS/TCP or FINS/UDP.
CX-Programmer
CX-Programmer
Ethernet Option Board
Ethernet Option Board
CX-Programmer
Router
Содержание CP1L CPU UNIT - 03-2009
Страница 1: ...Cat No W462 E1 06 CP1L CPU Unit SYSMAC CP Series CP1L L_0D_ CP1L M_0D_ OPERATION MANUAL...
Страница 2: ......
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Conformance to EC Directives 6...
Страница 70: ...36 Function Blocks Section 1 5...
Страница 584: ...550 Trouble Shooting Section 8 7...
Страница 627: ...593 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Страница 630: ...596 Sample Application Section 9 12...
Страница 654: ...620 Troubleshooting Unit Errors Section 11 4...
Страница 662: ...628 Replacing User serviceable Parts Section 12 2...
Страница 668: ...634 Standard Models Appendix A...
Страница 698: ...664 Auxiliary Area Allocations by Function Appendix C...
Страница 746: ...712 Auxiliary Area Allocations by Address Appendix D...
Страница 773: ...739 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 774: ...740 Connections to Serial Communications Option Boards Appendix F...
Страница 806: ...772 Index...
Страница 808: ...774 Revision History...