515
Auxiliary Area Allocations by Function
Appendix C
CPU Bus Unit Information
Special I/O Unit Information
Other PLC Operating Information
Duplication Error Flag
(fatal error)
A401.13
ON in the following cases:
• Two CPU Bus Units have been assigned the same unit
number.
• Two Special I/O Units have been assigned the same
unit number.
Read-only
CPM1A Unit Error Flags
A436.00 to
A436.06
ON when an error occurs in a CPM1A Expansion Unit or
Expansion I/O Unit.
A436.00: 1st Unit
A436.10: 2nd Unit
A436.02: 3rd Unit
A436.03: 4th Unit
A436.04: 5th Unit
A436.05: 6th Unit
A436.06: 7th Unit
Note
CPM1A-TS002 and CPM1A-TS102 are each
counted as two Units.
Read-only
Number of Connected
CPM1A Units
A437
Stores the number of CPM1A Expansion Units and
Expansion I/O Units connected as a hexadecimal num-
ber.
Note
This information is valid only when a Too Many
I/O Points error has occurred. CPM1A-TS002 and
CPM1A-TS102 are each counted as two Units.
Read-only
Name
Address
Description
Access
Updated
CPU Bus Unit Number
Duplication Flags
A410.00 to
A410.15
The Duplication Error Flag (A401.13) and the corre-
sponding flag in A410 will be turned ON when an CPU
Bus Unit’s unit number has been duplicated. Bits 00 to 15
correspond to unit numbers 0 to F.
Read-only
CPU Bus Unit Error, Unit
Number Flags
A417.00 to
A417.15
When an error occurs in a data exchange between the
CPU Unit and an CPU Bus Unit, the CPU Bus Unit Error
Flag (A402.07) is turned ON and the bit in A417 corre-
sponding to the unit number of the Unit where the error
occurred is turned ON. Bits 00 to 15 correspond to unit
numbers 0 to F.
Read-only
CPU Bus Unit Error Flag
(non-fatal error)
A402.07
ON when an error occurs in a data exchange between
the CPU Unit and an CPU Bus Unit (including an error in
the CPU Bus Unit itself).
Read-only
Name
Address
Description
Access
Updated
Special I/O Unit Number
Duplication Flags
A411.00 to
A416.15
The Duplication Error Flag (A401.13) and the corre-
sponding flag in A411 through A416 will be turned ON
when a Special I/O Unit’s unit number has been dupli-
cated.
Bits A411.00 to A416.15 correspond to unit numbers 000
to 05F (0 to 95).
Read-only
Special I/O Unit Setting
Error Flag
(non-fatal error)
A402.06
ON when an error occurs in a data exchange between
the CPU Unit and a Special I/O Unit (including an error in
the Special I/O Unit itself).
Read-only
Special I/O Unit Error, Unit
Number Flags
A418.00 to
A423.15
When an error occurs in a data exchange between the
CPU Unit and a Special I/O Unit, the Special I/O Unit
Error Flag (A402.06) will be turned ON.
Read-only
Name
Address
Description
Access
Updated
Battery Error Flag
(non-fatal error)
A402.04
ON if the CPU Unit’s battery is disconnected or its volt-
age is low and the Detect Battery Error setting has been
set in the PLC Setup.
Read-only
Cycle Time Too Long Flag
(fatal error)
A401.08
ON if the cycle time exceeds the maximum cycle time set
in the PLC Setup (the cycle time monitoring time).
Read-only
FPD Teaching Bit
A598.00
Turn this bit ON to set the monitoring time automatically
with the teaching function.
Read/write
Memory Corruption
Detected Flag
A395.11
ON when memory corruption is detected when the power
supply is turned ON.
Read-only
Name
Address
Description
Access
Updated
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...