391
Analog Input Units
Section 7-2
■
Set Data
• The Analog Input Unit will not start converting analog I/O values until the
range code has been written.
• Once the range code has been set, it is not possible to change the setting
while power is being supplied to the CPU Unit. To change the I/O range,
turn the CPU Unit OFF then ON again.
Averaging
Set whether averaging is to be used for set data. When the averaging bit is set
to 1, the average (moving average) for the past eight inputs is output as con-
version data.
Reading Analog Input
Conversion Values
Read the conversion value storage area with the ladder program. With word m
as the last input word allocated to the CPU Unit or an already-connected
Expansion Unit, the A/D conversion data will be output to the following words
m+1 to m+4.
Startup Operation
After the power is turned ON, it will require two cycle times plus approximately
50 ms before the first conversion data is stored in the input words. Therefore,
create a program as shown below, so that when operation begins simulta-
neously with startup it will wait for valid conversion data.
The analog input data will be 0000 until the initial processing is completed.
Handling Unit Errors
• When an error occurs in an Analog Input Unit, the analog input conversion
data becomes 0000.
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
15 0
1 0 0 0 0 0 0
8 7 6 5 4 3 2 1
0
0
Set to 1.
Set to 1.
Wd (n+1)
Wd (n+2)
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Averaging
0
No
1
Yes
Input Use
0
No
1
Yes
Range code
Analog input signal range
−
10 to 10 V
0 to 10 V
1 to 5 V or 4 to 20 mA
0 to 5 V or 0 to 20 mA
00
01
10
11
MOV(021)
2
D 0
T 5
#0002
T5
Power ON
P_On
TIM5 is started when the power is
turned ON. After 0.1 to 0.2 s (100 to
200 ms) elapses, the TIM5 contact
turns ON and the analog input 1 con-
version data stored in word 2 is trans-
ferred to DM0.
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...