manualshive.com logo in svg
background image

Liebert

®

 IntelliSlot

 Unity

 Card

User Manual—Web, SNMP, Modbus, BACnet, YDN23

Содержание Liebert Intellislot Unity Card

Страница 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 ...

Страница 2: ......

Страница 3: ...words Immediately 10 2 3 Configure the Card 11 2 4 Installing Multiple Liebert IntelliSlot Unity Cards in a System 12 2 5 Security Best Practices 13 3 0 Enable Communication Protocols 15 3 1 Enable Protocols 15 3 1 1 Enable Modbus Protocol 16 3 1 1 1 Configure Modbus TCP 17 3 1 1 2 Configure Modbus RTU 18 3 1 2 Enable BACnet Protocol 19 3 1 2 1 Configure BACnet IP Protocol 20 3 1 2 2 Configure BAC...

Страница 4: ...5 2 Communications Active Events Folder 40 5 3 Communications Downloads Folder 40 5 4 Communications Configuration Folder 40 5 4 1 Configuration System Folder 41 5 4 1 1 Time Service Settings 41 5 4 2 Configuration User Folder 42 5 4 3 Configuration Network Folder 42 5 4 3 1 IPv4 IPv6 43 5 4 3 2 Domain Name Server DNS Test 44 5 4 4 Configuration Web Server Folder 45 5 4 4 1 Certificate 46 5 4 4 1 ...

Страница 5: ...r 60 5 5 3 1 SNMPv3 User Folder 62 5 5 3 2 Editing the SNMPv3 Table 64 5 5 3 3 SNMPv1 Trap Folder 65 5 5 3 4 SNMPv1 v2c Access Folder 66 5 5 4 Protocols YDN23 Folder 67 5 6 Communications Status Folder 68 5 7 Communications Support Folder 69 5 7 1 Support Active Networking Folder 71 5 7 2 Support Firmware Update Folder 73 6 0 Firmware Updates 75 6 1 Updating the Liebert IntelliSlot Unity Card s Fi...

Страница 6: ...Liebert IntelliSlot Unity Card User Manual iv Page intentionally left blank ...

Страница 7: ... UPS example 30 Figure 4 2 Web page sections Thermal Management unit example 30 Figure 4 3 Managed Device Web page without sensors 31 Figure 4 4 Help text on mouse over 32 Figure 4 5 Managed Device tab examples Liebert GXT4 and Liebert CRV 33 Figure 4 6 Sensor tab menu 35 Figure 4 7 Sensor tab Summary page layout 36 Figure 4 8 Sensor details Door closure and temperature sensor examples 37 Figure 4...

Страница 8: ...Liebert IntelliSlot Unity Card User Manual vi Page intentionally left blank ...

Страница 9: ... 1 2 Liebert IntelliSlot card communication protocols 4 Table 2 1 Settings to review and verify to reduce risk of unauthorized access to critical infrastructure equipment 13 Table 2 2 Ports used by the Unity card 14 Table 4 1 Help text and icons 31 Table 4 2 Communications tab menus 34 Table 4 3 Sensor tab folders 35 ...

Страница 10: ...Liebert IntelliSlot Unity Card User Manual viii Page intentionally left blank ...

Страница 11: ...ify with a voltmeter that power is off and wear appropriate personal protective equipment per NFPA 70E before working within the electric control enclosure WARNING Risk of electric shock Can cause equipment damage injury or death Open all local and remote electric power supply disconnect switches and verify with a voltmeter that power is off before working within any electric connection enclosures...

Страница 12: ...Important Safety Instructions Liebert IntelliSlot Unity Card User Manual 2 Page intentionally left blank ...

Страница 13: ...ty DP card features 1 1 Protocols Each card supports the Emerson Protocol Remote Service Delivery Protocol and HTTP Web by default The Liebert IntelliSlot Unity DP supports selecting two third party protocols the Liebert IntelliSlot Unity LIFE card supports the default protocols only Emerson Protocol Remote Service Delivery Protocol and HTTP Web Available protocols are BACnet IP BACnet over Intern...

Страница 14: ...roducts MIB on the network management station NMS The Liebert Global Products MIB is available at Liebert s Web site www liebert com it supports both Windows 192436P1 and Unix 192435P1 file formats Web Support The Liebert IntelliSlot Unity card delivers Web management and control to Liebert equipment over HTTP and HTTPS All authorized users on your network will be able to view status information T...

Страница 15: ...nformation to the Trellis DCIM platform Trellis can manage and control Liebert equipment using SNMP Modbus or the Emerson Protocol This allows monitoring all Liebert equipment using Liebert IntelliSlot Web Liebert IntelliSlot 485 Liebert IntelliSlot IPBML Liebert IntelliSlot Web ADPT or Liebert IntelliSlot Unity platform communication interfaces Liebert Nform Support Utilizing the Emerson Protocol...

Страница 16: ...Introduction Liebert IntelliSlot Unity Card User Manual 6 Page intentionally left blank ...

Страница 17: ...t IntelliSlot bay on your Liebert equipment It may have a plastic cover 2 Insert the card into the Liebert IntelliSlot bay 3 Secure the card with the screws supplied with the cover plate WARNING Risk of arc flash and electric shock Can cause injury or death Open all local and remote electric power supply disconnect switches verify with a voltmeter that power is off and wear appropriate personal pr...

Страница 18: ...ator is not available or there is no way of determining the IP address assigned by the DHCP server use a computer with a direct Ethernet connection to the Liebert IntelliSlot Unity card and the Autoconfiguration IPv4 Address convention described in 2 1 2 Connect an Ethernet Cable to access the card s Web page and configure the card To see the card s last DHCP assigned IP address click the Communic...

Страница 19: ... serial cable connection will be used Liebert IntelliSlot Unity cards come with an Adapter RJ 45 2POS Terminal Block The adapter has two screw terminals to attach the ends of a RS 485 cable for communicating to a building management system 1 Find the serial cable from the building management system If it already has an RJ 45 connector on the end determine whether it uses the same pin out as the Li...

Страница 20: ...s are valid except The general user name and password are also set at the factory User and User case sensitive The general user has access only to non protected configuration and control areas of the Liebert IntelliSlot Unity card To change the user names and passwords 1 Select the Communications tab Configuration User 2 Click the Edit button and enter the factory set administrator user name Liebe...

Страница 21: ...n interface refer to Figure 2 3 1 Select Communications tab Configuration Network 2 Enable the protocol either IPv4 or IPv6 that will be used to communicate with the Liebert IntelliSlot Unity card and with the Liebert equipment a Click either IPv4 or IPv6 b Click Edit c When prompted with a login display enter the user name and password the defaults are Liebert and Liebert d Click to check enabled...

Страница 22: ...Follow instructions in the user manual for the first card If the first and second cards are both Liebert IntelliSlot Unity cards steps must be taken to avoid duplicate Emerson Protocol MSTP node IDs By default the two cards would use the same node ID and one or both cards would report a duplicate node error and fail to communicate with the system The default node ID for a Liebert IntelliSlot Unity...

Страница 23: ... Folder Web Service Protocol Select HTTPS to use SSL encryption when accessing data through the web user interface 5 4 4 Configuration Web Server Folder SSL Certificates When using HTTPS install your own SSL Certificates from a trusted certificate authority or generate alternative self signed certificates 5 4 4 1 Certificate Password Protect Web Access Enable to require users to login before any d...

Страница 24: ...figure SNMPv1 Trap Settings and 3 1 3 1 4 Configure SNMPv1 v2c Access Settings SNMPv3 Settings Use the SNMPv3 Authentication and Privacy settings to make SNMPv3 communications more secure 3 1 3 1 2 Configure SNMPv3 User Settings YDN23 Settings Set Managed Device Write Access to Read Only to prevent changes to the device through the YDN23 interface 5 5 4 Protocols YDN23 Folder Emerson Protocol Sett...

Страница 25: ...ut a check mark next to the protocols to use Only two may be enabled only one of the two can use the 485 port 4 Click Save to confirm the changes or Cancel to discard them NOTE No more than two protocols may be enabled on one card Only one version of BACnet may be selected either BACnet IP or BACnet MSTP Only one version of Modbus may be selected either Modbus TCP or Modbus RTU Only one of the pro...

Страница 26: ...col Protocols may be enabled after a card has been installed and configured 1 Select Communications tab Protocols Modbus 2 Click Edit and enter a User name and password 3 Select the access level Read Only or Read Write 4 Select the Modbus interface Modbus TCP or Modbus RTU 5 Click Save to confirm the changes or Cancel to discard them 6 Configure the Modbus interface chosen See 3 1 1 1 Configure Mo...

Страница 27: ... TCP Folder for additional details 4 Enter the Port to be used by the Modbus Server to listen for and respond to Modbus protocol requests based on limit Network Access Type setting 5 Enter the Maximum Client Connection Count 6 Click Save to confirm the changes or Cancel to discard them 7 Restart the card to confirm the changes a Select Communications tab Support b Enable the commands c Click Resta...

Страница 28: ...ng devices connected through the RS 485 interface The default baud rate is 9600 19200 and 38400 are also available For additional description of the settings see 5 5 2 2 Modbus RTU Folder 4 Click Save to confirm the changes or Cancel to discard them 5 Restart the card to confirm the changes a Select Communications tab Support b Enable the commands c Click Restart Figure 3 3 Modbus RS 485 NOTE Cont...

Страница 29: ...oose the BACnet interface BACnet IP or BACnet MSTP 5 Set the Device Object Instance Number 6 Set the Device Object Name 7 Set the APDU Timeout 8 Set the APDU Retries 9 Click Save to confirm the changes or Cancel to discard them 10 Configure the BACnet interface chosen see 3 1 2 1 Configure BACnet IP Protocol or 3 1 2 2 Configure BACnet MSTP Protocol For description of the settings see 5 5 1 Protoc...

Страница 30: ...an network or other third party monitoring service a Choose whether or not to enable Register as Foreign Device b Enter the IP address of the BBMD BACnet Broadcast Management Device c Enter a time in seconds for Foreign Device Time to Live For descriptions of the settings see 5 5 1 1 BACnet IP Folder 4 Click Save to confirm the changes or Cancel to discard them 5 Restart the card to activate the c...

Страница 31: ...ted through the RS 485 interface 4 Set the BACnet MSTP Data Rate 5 Set the BACnet MSTP Max Master Address 6 Set the BACnet MSTP Max Info Frames For descriptions of the settings see 5 5 1 2 BACnet MSTP Folder 7 Click Save to confirm the changes or Cancel to discard them 8 Restart the card to activate the changes a Select Communications tab Support b Enable the commands c Click Restart Figure 3 6 BA...

Страница 32: ...equired 3 To enable Authentication Traps click to check mark the box 4 To change the Heartbeat Trap Interval choose a time from the drop down list or choose Disabled to prevent any heartbeat traps from being sent The interval times offered are 5 minutes 30 minutes or 1 4 8 12 or 24 hours 5 For each trap choose whether or not to disable or set the interval to one of the periods on the menu For desc...

Страница 33: ...ess Optionally you can select a text based ID instead 1 Select Communications tab Protocols SNMP 2 Click Edit and enter a User name and password if required 3 Edit the settings Refer to 5 5 3 Protocols SNMP Folder page 60 for descriptions of the settings and options In SNMPv3 Engine ID Format Type select MAC Address or Text If you selected Text type the text on which the generated engine ID will b...

Страница 34: ...er name and password if required 3 Enter the information and set the permissions appropriate to the user Figure 3 9 For descriptions of the settings and options see 5 5 3 1 SNMPv3 User Folder page 62 4 Click Save to confirm the changes or click on Cancel to discard them 5 Repeat Steps 1 through 4 for additional users 6 Restart the card to activate the changes a Select the Communications tab Suppor...

Страница 35: ...and set the permissions appropriate to the user Figure 3 10 For descriptions of the settings see 5 5 3 3 SNMPv1 Trap Folder 4 Click Save to confirm the changes or Cancel to discard them 5 Repeat Steps 1 through 4 for any additional users 6 Restart the card to confirm the changes a Select the Communications tab Support b Enable the commands c Click Restart Figure 3 10 SNMPv1 trap settings Settings ...

Страница 36: ...ssions appropriate to the user Figure 3 10 For description of the settings and options see 5 5 3 4 SNMPv1 v2c Access Folder page 66 4 Click Save to confirm the changes or Cancel to discard them 5 Restart the card to confirm the changes The card must be restarted before another user s settings may be changed a Select the Communications tab Support b Enable the commands c Click Restart Figure 3 11 S...

Страница 37: ...he Managed Device tab then Summary Downloads The Data Mapping Files heading shows mapping files for each enabled protocol BACnetDataMap txt for BACnet IP and BACnet MSTP ModbusDataMap txt for Modbus TCP and Modbus RTU SNMP_Events txt SNMP_Parameters txt SNMP_upsMibEvents txt and SNMP_upsParams txt for SNMP v1 v2c v3 Ydn23DataMap txt for YDN23 More information about BACnet and Modbus protocol mappi...

Страница 38: ...Enable Communication Protocols Liebert IntelliSlot Unity Card User Manual 28 Page intentionally left blank ...

Страница 39: ... have been installed The tab selected determines the menu shown Managed Device tab Information pertaining to the equipment being monitored and controlled Refer to 4 3 Managed Device Tab Menus for details The tab label refers to the type of Liebert unit the card is installed in For example the Managed Device tab for a card installed in a Liebert GXT4 1000 RT120 UPS will be labeled GXT4 1000 RT120 s...

Страница 40: ...ions Thermal Management unit example Identification Status Status of equipment sensors if any are installed and communications Tab Menu changes according to monitored equipment Communications Tab Managed Device Tab Card in a Liebert GXT4 Information on the Opening Screen depends on type of unit being monitored Sensor Tab Identification Status Tab Menu changes according to monitored equipment Infor...

Страница 41: ...the left of the Status Events or Settings row as shown below The Web page may display any of six icons beside the Status Events or Setting entry Table 4 1 Help text and icons Icon Description a check mark on a green button Event Normal an i on a blue button Event Information an x on a red button Event Alarm an exclamation point on a yellow shield Event Warning an exclamation point on a red button ...

Страница 42: ...iebert IntelliSlot Unity Card User Manual 32 Figure 4 4 Help text on mouse over Hovering a mouse pointer over the icon reveals information about that entry Help text about the System Input Nominal Frequency entry on the Managed Device Tab Input Menu ...

Страница 43: ...ed in Thermal Management equipment Information on those menus will also differ depending on the equipment the card is installed in Figure 4 5 Managed Device tab examples Liebert GXT4 and Liebert CRV The Managed Device Tab will display Status or Events for the applicable equipment only Power information is shown in this Managed Device Tab for a UPS The Managed Device Tab will display Status Events ...

Страница 44: ...E needs to be reconfigured RS 485 Port Conflict Duplicate Emerson Protocol MSTP Node ID Duplicate BACnet MSTP Node ID Shows the overall condition of the system and whether a restart is needed to activate configuration changes restart is performed only from the Support Folder page 68 Support Agent time and Date Agent Model Agent App Firmware Version Agent App Firmware Label Agent Boot Firmware Vers...

Страница 45: ...nloads Displays a list of text files that can be downloaded The files available are dependent on the current state of the card Sensor Server System Model Number System Status Too Many Sensors Slots Not Available Acknowledge Sensor Changes Displays overall information about the sensors Sensor Change Lists events showing sensors that have been added or removed If the list has any entries an Acknowle...

Страница 46: ...ents may also be acknowledged on this window Figure 4 7 Sensor tab Summary page layout 4 5 2 Sensor Tab Summary Page Details Pane The Details pane of the Sensor tab window appears when the Summary folder is selected The area shows the status of all connected sensors see Figure 4 7 Supported sensors include Temperature Humidity Door Closure Contact Closure Leak Detection Temperature sensor selected...

Страница 47: ...temperature values is defined in the Display Temperature Units setting under Communications tab Configuration System See 5 4 1 Configuration System Folder Details for the sensors include the current state or reading event status and whether the reading is above or below the threshold established in the Settings pane Figure 4 8 Sensor details Door closure and temperature sensor examples Click Edit ...

Страница 48: ... Enter the user name and password 4 Select the sensor to be moved higher or lower in the list The radio button beside the sensor to be changed is highlighted 5 Use the arrows at the right side of the list to move the sensor up or down 6 Click Save Repeat the steps for any other sensors to be moved higher or lower in the list Figure 4 9 Changing sensor order This arrow moves the selected sensor hig...

Страница 49: ...nd enter the card s IP address 2 Click the Communications tab 3 Select the menu in the Tab Menu area Figure 5 1 that contains the configuration setting to be changed 4 Click the Edit button near the top of the page 5 Enter the administrator name and password for the Liebert IntelliSlot Unity card in the dialog box that opens the default settings are Liebert and Liebert 6 Click OK 7 Change the sett...

Страница 50: ...lays events affecting the Liebert IntelliSlot Unity card 5 3 Communications Downloads Folder The Communications tab s Downloads folder contains no configurable settings The folder displays links to download logs of third party protocols that are enabled on the Liebert IntelliSlot Unity card The logs help in configuring and troubleshooting communication between the Network Management or Building Ma...

Страница 51: ...r Time Service Each setting offers either a menu of choices or an enable disable check box Users can set these parameters Figure 5 3 Configuration folder System subfolder Time Service Time Service setting options External Time Source The external source to be used for time synchronization NTP Time Server Network Time Server NTP URL or IP address NTP Time Sync Rate The rate at which time will be sy...

Страница 52: ...d the changes 5 4 3 Configuration Network Folder The top level of the Network subfolder displays Speed Duplex Domain Name Suffix List Telnet Server The Speed Duplex item selects the speed and duplex configuration of the card s Ethernet port It is set to Auto by default If it requires changing contact the system administrator for the proper settings The Domain Name Suffix List is a listing of domai...

Страница 53: ...6 settings IPv4 Settings IPv4 Protocol Enables IPv4 in the card IP Address Method Mode the card boots into to be a network ready device Static DHCP BootP Static IP Address Network address for the interface Subnet Mask Network mask for the interface which divides a network into manageable segments Default Gateway IP address of the gateway for network traffic destined for other networks or subnets D...

Страница 54: ...dress Source Source of DNS server identification None Automatic Configured Primary DNS Server Secondary DNS Server 5 4 3 2 Domain Name Server DNS Test The Domain Name Server Test checks key points of a Domain Name Server DNS setup for a given domain Domain Name Server DNS Test Settings Last Query Response Response from a domain name server DNS to the last query Example gxtwebdemo liebert com resol...

Страница 55: ...ess to data on all Unity card web pages when the user is logged in with Administrator credentials When disabled write access is restricted to web browsers connected on an Autoconfiguration IPv4 address An Autoconfiguration IPv4 address is of the form 169 254 x x and is negotiated automatically when a direct connection is made between the Ethernet port of your PC and the Ethernet port of the Unity ...

Страница 56: ...SL certificate files that were generated by their own Certificate Authority CA Selections in Certificate Figure 5 6 provide commands to Upload SSL Certificate PEM Files or Generate Self Signed SSL Certificate Figure 5 6 Certificate Certificate Commands Upload SSL Certificate PEM Files Uploads and installs a PEM encoded SSL key file and certificate file that were generated by a trusted Certificate ...

Страница 57: ...ly generate a certificate Common Name Fully qualified domain name that browser clients will use to reach the card s web server when it is running with the certificate generated with the name entered here Organization Organization or company identified as the owner of the generated certificate Organizational Unit Organizational unit or company division of the organization identified as the owner of...

Страница 58: ...Certificate PEM Files dialog 5 4 4 1 2 Generating a Self signed SSL Certificate 1 Select Communications tab Configuration Web Server Certificate 2 In the Settings section a Click Edit b In Generate Self Signed SSL Certificate Mode select the mode to use If you select User Configured Settings make entries in all of the configurable value fields required then click Save 3 In the Commands section cli...

Страница 59: ...ormation about the LIFE settings refer to Appendix A Configuration Folder LIFE Sub Folder 5 4 6 Configuration Emerson Protocol Folder Emerson Protocol contains four subfolders Managed Device MSTP Ethernet and Internal Emerson Protocol options Emerson Protocol IP Access When disabled prevents access from a remote IP based system using the Emerson Protocol NOTE With the exception of changing the nod...

Страница 60: ...l and text messaging about events The subfolder also contains a test to determine if email and text messages can be successfully sent Settings for the two messaging methods permit specifying who gets the messages the format or the messages and other details Messaging options Email May be enabled to send email messages about events SMS May be enabled to send text messages about events ...

Страница 61: ...e Support company com Email To Address Email address of the recipient Multiple email addresses should be separated by a semicolon Email Subject Type Subject of the email This value will default to the event description The subject line can be customized Custom Subject Text The subject of the email can be changed SMTP Server Address Fully qualified domain name or IP address of the server used for r...

Страница 62: ...ion will be included in outgoing messages Include Name in Message If checked the agent card Name will be included in outgoing messages Include Contact in Message If checked the agent card Contact will be included in outgoing messages Include Location in Message If checked the agent card Location will be included in outgoing messages Include Description in Message If checked the agent card Descript...

Страница 63: ...e number of buffered events reaches the Consolidation Event Limit 5 4 7 2 SMS Selections in SMS determine how the card sends text messages about events SMS Settings SMS From Address Sender s SMS address In most cases this will be the SMS address of the person to whom replies should be sent For example Support company com SMS To Address SMS address of the recipient Multiple SMS addresses should be ...

Страница 64: ...use when SMS SMTP authentication is enabled Include IP Address in Message If checked the IP Address of the agent card will be included in outgoing messages Include Event Description in Message If checked SNMP event description will be included in outgoing messages Include Name in Message If checked the agent card Name will be included in outgoing messages Include Contact in Message If checked the ...

Страница 65: ...mit If Event Consolidation is enabled a message will be sent when Consolidation Time Limit seconds has passed since the first buffered event was received Consolidation Event Limit If Event Consolidation is enabled a message will be sent when the number of buffered events reaches the Consolidation Event Limit 5 4 7 3 Messaging Test Selections here permit testing the setup for email and SMS messages...

Страница 66: ...me Some protocols may not be available for some types of managed devices see 1 2 Compatibility With Other Emerson Products and Communication Protocols The Liebert IntelliSlot Unity card allows selecting two third party protocols The folders contained by the Protocols folder are BACnet BACnet IP BACnet MSTP Modbus Modbus TCP Modbus RTU SNMP SNMPv3 User 20 SNMPv1 Trap 20 SNMPv1 v2c Access 20 YDN23 S...

Страница 67: ... to write to the managed device BACnet Interface BACnet server interface BACnet IP or BACnet MSTP Device Object Instance Number The instance number 0 4194302 of the BACnet server s device object Device Object Name The name of the BACnet server s device object APDU Timeout The timeout in milliseconds between APDU retries 1 65535 APDU Retries The number of times to retransmit an APDU after the initi...

Страница 68: ...ddress of the BACnet Broadcast Management Device BBMD to be accessed for Foreign Device Registration Foreign Device Time to Live Time to remain in the BBMD Foreign Device table after registration 5 5 1 2 BACnet MSTP Folder BACnet MSTP Settings Node ID The BACnet server s MS TP node ID MAC Data Rate The BACnet MSTP communication rate bits per second Max Master Address The maximum node ID MAC in use...

Страница 69: ...s TCP Folder The Modbus TCP permits connection to the card by any client Open permits communication by any IP address clients on the same subnet as the Liebert IntelliSlot Unity card clients with specific IP addresses Trusted IP Lists only five addresses are permitted Modbus TCP Settings Limit Network Access Type IP Access List Open Same Subnet Trusted IP List Port The TCP port used by the Modbus ...

Страница 70: ...ion rate 9600 19200 38400 Parity Check The communication parity check None Even Odd 5 5 3 Protocols SNMP Folder Folders and settings in this folder permit configuring the card for various types of SNMP communication including access traps and other user settings SNMP Settings SNMPv3 Engine ID Read only The generated SNMPv3 engine ID Note A newly generated ID appears only after rebooting the card S...

Страница 71: ...obal Products LGP MIB Enable or Disable support for getting and setting data using the Liebert Global Products MIB LGP MIB Traps Enable or Disable support for Liebert Global Products MIB traps Note LGP traps will not be sent unless LGP MIB is enabled LGP MIB System Notify Trap Enable or Disable support for the LGP System Notification trap This is a single trap sent each time an alarm or warning is...

Страница 72: ...es effective click Cancel to discard the changes SNMPv3 User Settings SNMPv3 User Enable Select to enable read write or sending notifications with the user s credentials SNMPv3 Username The User name the authentication and privacy settings apply to This string can be composed of printable characters except colon tab double quote and question mark SNMPv3 Access Type Read Only Read Write or Traps on...

Страница 73: ...et request This string can be composed of printable characters with the exception of colon tab double quote and question mark Note The entry must be 8 or more characters but not more than 64 SNMPv3 Trap Target Addresses Network hosts that will receive SNMPv3 traps identified with either a network name or IP address Multiple addresses must be separated by commas SNMPv3 Trap Port Port used by the ta...

Страница 74: ...rk in the boxes beside the desired information see Figure 5 9 The choices permit showing the same information in this screen that is displayed by clicking on a SNMPv3 User Settings folder or a SNMPv3 User Settings link Figure 5 9 Edit the SNMPv3 table Click on this link to change the information shown in the table Checking all choices will display the information below on the SNMPv3 User page The ...

Страница 75: ...ts Also data shown in the table may be changed by clicking on the link above the table SNMPv1 Trap Settings SNMP Trap Target Addresses Configure network hosts that will receive alert notifications i e SNMP Traps The host can be identified as either an IP address or the host s network name SNMP Trap Port Port used by the target host for receiving notifications default is 162 SNMP Trap Community Str...

Страница 76: ... on the folders for the access hosts Also data shown in the table may be changed by clicking on the link above the table SNMPv1 v2c Access Settings SNMP Access IP Address Configure network hosts interested in device information access The host can be identified as either an IP address or the host s network name SNMP Access Type SNMPv1 v2C access type Read Only or Read Write SNMP Access Community S...

Страница 77: ...cols YDN23 Folder The YDN23 protocol supported is based on the YD T 1363 specification using an RS 485 network connection YDN23 Protocol settings Managed Device Write Access Enable or Disable the YDN23 server to write to the managed device Device Address YDN23 device address Baud Rate The communications rate in bps ...

Страница 78: ...r Manual 68 5 6 Communications Status Folder The Status folder contains no configurable items It displays the System Status of the Liebert IntelliSlot Unity card and a list of events that affect the card s status A green check mark indicates the status is Normal as shown in the Status column ...

Страница 79: ...nity card The folder also displays information about the card for help in troubleshooting such as the card s firmware version label MAC address and related information Support Folder Settings Agent Date and Time Date and time setting for the card Agent Model The card s model Unity Platform Agent App Firmware Version The card s firmware version 2 0 or higher Agent App Firmware Label The card s firm...

Страница 80: ...is a proprietary reference document for device data FDM Version The card s FDM version the FDM is a data model document that defines data supported by devices that use the Emerson Protocol Product Sequence ID The card s product sequence identifier Commands Enable Cancel Restart Card Restart card and implement configuration changes Reset Card to Factory Defaults Reset the card s configuration to it...

Страница 81: ...ernet MAC Address Ethernet MAC Address for the Liebert IntelliSlot card IPv4 Address Presently used IPv4 network address IPv4 Default Gateway Presently used IPv4 network address of the gateway for network traffic destined for other networks or subnets Primary DNS Presently used IPv4 Primary DNS Secondary DNS Presently used IPv4 Secondary DNS Last DHCP BOOTP Address Last known IPv4 address assigned...

Страница 82: ...t combining Prefix with EUI 64 MAC Link Local Presently used IPv6 Link Local Address IPv6 Default Gateway Presently used IPv6 network address of the gateway for network traffic destined for other networks or subnets Primary DNS Server IPv6 Primary DNS Secondary DNS Server Presently used IPv6 Secondary DNS Last DHCPv6 Last known IPv6 address assigned by DHCPv6 Last DHCPv6 Lease Lease time of last k...

Страница 83: ... current firmware is not the initial load Firmware Update settings Current Firmware Version The version of the firmware running on the card Current Firmware Label The label of the firmware running on the card Current Firmware Date The build date of the firmware running on the card Alternate Firmware Version The version of the firmware in the alternate area Alternate Firmware Label The label of the...

Страница 84: ...ert IntelliSlot Unity Card User Manual 74 Firmware Commands Run Alternate Firmware Return the card s firmware to a version in the alternate area the version in use before the most recent firmware update Firmware Update Update the card s firmware to a new version ...

Страница 85: ...e a known IP address and it is configured for DHCP connect the card to a computer with an Ethernet cable and open a Web browser The card has an Ethernet RJ 45 connector on the front see Figure 6 1 The card and computer will automatically negotiate communications which will take about one minute for details on auto configuration see 2 1 2 Connect an Ethernet Cable When communication is established ...

Страница 86: ...mware button Figure 6 2 Firmware update screen NOTE Do not navigate away from the Firmware Update screen and do not close the browser once the update begins Either action will interrupt the download Support Folder Firmware Update Web button becomes active when enabled and administrator s user name and password are entered Enable Button User name and password must be entered to update firmware ...

Страница 87: ...ct the Enable button 4 Enter the user name and password in the security dialog box that appears use the administrator user name and password from the user settings 5 Click the Run Alternate button A confirmation dialog opens 6 Click OK on the confirmation dialog NOTE Reverting to an alternate firmware version will not be possible if the currently operating firmware is the initial version loaded on...

Страница 88: ...Firmware Updates Liebert IntelliSlot Unity Card User Manual 78 Page intentionally left blank ...

Страница 89: ...ncoming calls Next Call Date and Time Date and Time of next call to make to the LIFE Watch Station server Call Interval Days Days between routine calls to LIFE Watch Station Call Interval Hours Number of hours between LIFE Watch Station routine calls Call Interval Minutes Number of minutes between routine LIFE Watch Station calls This value is used in conjunction with val_life_callInterval_hours C...

Страница 90: ...IFE Gate Port Number Status Description Device State Whether the device is connected or unconnected Connection Status The connection status of the Remote Service Delivery application system interface This is the interface by which Remote Service Delivery services communicates with the Unity system software Call Type The type of call currently in progress with the LIFE Watch Station server Schedule...

Страница 91: ......

Страница 92: ... Sacco PD Italy 39 049 9719 111 Fax 39 049 5841 257 Asia 7 F Dah Sing Financial Centre 108 Gloucester Road Wanchai Hong Kong 852 2572220 Fax 852 28029250 While every precaution has been taken to ensure the accuracy and completeness of this literature Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omi...

Отзывы: