Enable Communication Protocols
19
Liebert
®
IntelliSlot
™
Unity
™
Card User Manual
3.1.2
Enable BACnet Protocol
1. Select
Communications
tab >
Protocols
>
BACnet
.
2. Click
Edit
and enter a user name and password if required.
3. Enter the
Managed Device Write Access level
(
Read Only
or
Read/Write
).
This determines a user’s ability to change settings in the Liebert IntelliSlot Unity card.
4. Choose the
BACnet interface
:
BACnet
IP
or
BACnet MSTP
.
5. Set the
Device Object Instance Number
.
6. Set the
Device Object Name
.
7. Set the
APDU Timeout
.
8. Set the
APDU Retries
.
9. Click
Save
to confirm the changes or
Cancel
to discard them.
10. Configure the BACnet interface chosen, see
3.1.2.1 - Configure BACnet IP Protocol
Configure BACnet MSTP Protocol
.
For description of the settings, see
5.5.1 - Protocols—BACnet Folder
.
Figure 3-4 BACnet protocol settings
NOTE
Contact your system administrator or building management system administrator if you are
uncertain about the settings.
Содержание Liebert Intellislot Unity Card
Страница 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 ...
Страница 2: ......
Страница 6: ...Liebert IntelliSlot Unity Card User Manual iv Page intentionally left blank ...
Страница 8: ...Liebert IntelliSlot Unity Card User Manual vi Page intentionally left blank ...
Страница 10: ...Liebert IntelliSlot Unity Card User Manual viii Page intentionally left blank ...
Страница 12: ...Important Safety Instructions Liebert IntelliSlot Unity Card User Manual 2 Page intentionally left blank ...
Страница 16: ...Introduction Liebert IntelliSlot Unity Card User Manual 6 Page intentionally left blank ...
Страница 38: ...Enable Communication Protocols Liebert IntelliSlot Unity Card User Manual 28 Page intentionally left blank ...
Страница 88: ...Firmware Updates Liebert IntelliSlot Unity Card User Manual 78 Page intentionally left blank ...
Страница 91: ......