Enable Communication Protocols
17
Liebert
®
IntelliSlot
™
Unity
™
Card User Manual
3.1.1.1 Configure Modbus TCP
1. Select the
Communications
tab >
Protocols
>
Modbus TCP
.
2. Click
Edit
and enter a User name and password if required.
3. Set the
Limit Network Access Type
by choosing from the drop-down list
(
Open
/
Same Subnet
/
Trusted IP List
).
Refer to
for additional details.
4. Enter the
Port
to be used by the Modbus Server to listen for and respond to Modbus protocol requests
based on limit Network Access Type setting.
5. Enter the
Maximum Client Connection Count
.
6. Click
Save
to confirm the changes or
Cancel
to discard them.
7. Restart the card to confirm the changes.
a. Select
Communications
tab >
Support
.
b. Enable the commands.
c. Click
Restart
.
Figure 3-2 Modbus TCP-Trusted IP List
... brings up a screen
where this information
may be entered.
Clicking on
one of the five
Trusted IP
List folders...
Содержание Liebert Intellislot Unity Card
Страница 1: ...Liebert IntelliSlot Unity Card User Manual Web SNMP Modbus BACnet YDN23 ...
Страница 2: ......
Страница 6: ...Liebert IntelliSlot Unity Card User Manual iv Page intentionally left blank ...
Страница 8: ...Liebert IntelliSlot Unity Card User Manual vi Page intentionally left blank ...
Страница 10: ...Liebert IntelliSlot Unity Card User Manual viii Page intentionally left blank ...
Страница 12: ...Important Safety Instructions Liebert IntelliSlot Unity Card User Manual 2 Page intentionally left blank ...
Страница 16: ...Introduction Liebert IntelliSlot Unity Card User Manual 6 Page intentionally left blank ...
Страница 38: ...Enable Communication Protocols Liebert IntelliSlot Unity Card User Manual 28 Page intentionally left blank ...
Страница 88: ...Firmware Updates Liebert IntelliSlot Unity Card User Manual 78 Page intentionally left blank ...
Страница 91: ......