338
Serial Communications
Section 6-1
Error Codes
The following error codes are stored in an allocated DM Area word when an
error occurs in Modbus-RTU Easy Master function execution.
Auxiliary Area Flags
and Bits
The Modbus-RTU command set in the DM fixed allocation words for the Mod-
bus-RTU Easy Master is automatically sent when the Modbus-RTU Master
Execution Bit is turned ON. The results (normal or error) will be given in corre-
sponding flags.
Code
Name
Description
0x00
Normal end
Not an error.
0x01
Illegal address
The slave address specified in the parameter
is illegal (248 or higher).
0x02
Illegal function code
The function code specified in the parameter is
illegal.
0x03
Data length overflow
There are more than 94 data bytes.
0x04
Serial communica-
tions mode error
The Modbus-RTU Easy Master function was
executed when the serial communications
mode was not the Serial Gateway Mode.
0x80
Response timeout
A response was not received from the Servo.
0x81
Parity error
A parity error occurred.
0x82
Framing error
A framing error occurred.
0x83
Overrun error
An overrun error occurred.
0x84
CRC error
A CRC error occurred.
0x85
Incorrect confirmation
address
The slave address in the response is differ-
ence from the one in the request.
0x86
Incorrect confirmation
function code
The function code in the response is difference
from the one in the request.
0x87
Response size over-
flow
The response frame is larger than the storage
area (92 bytes).
0x88
Exception response
An exception response was received from the
slave.
0x89
Service being exe-
cuted
A service is already being executed (reception
traffic congestion).
0x8A
Execution canceled
Executing the service has been canceled.
0x8f
Other error
Other FINS response code was received.
Word
Bit
Port
Contents
A640
00
Port 2
Modbus-RTU Master Execution Bit
Turned ON: Execution started
ON: Execution in progress.
OFF: Not executed or execution completed.
01
Modbus-RTU Master Execution Normal Flag
ON: Execution normal.
OFF: Execution error or still in progress.
02
Modbus-RTU Master Execution Error Flag
ON: Execution error.
OFF: Execution normal or still in progress.
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...