221
High-speed Counters
Section 5-2
Set the target values so that they do not occur at the peak or trough of count
value changes.
Range Comparison
The specified interrupt task is executed when the high-speed counter PV is
within the range defined by the upper and lower limit values.
• The comparison conditions (upper and lower limits of the range) are regis-
tered in the comparison table along with the corresponding interrupt task
number. The specified interrupt task will be executed once when the high-
speed counter PV is in the range (Lower limit
≤
PV
≤
Upper limit).
• A total of 8 ranges (upper and lower limits) are registered in the compari-
son table.
• The ranges can overlap.
• A different interrupt task can be registered for each range.
• The counter PV is compared with the 8 ranges once each cycle.
• The interrupt task is executed just once when the comparison condition
goes from unmet to met.
Restrictions
When more than one comparison condition is met in a cycle, the first interrupt
task in the table will be executed in that cycle. The next interrupt task in the
table will be executed in the next cycle.
Note The range comparison table can be used without starting an interrupt task
when the comparison condition is met. The range comparison function can be
useful when you just want to know whether or not the high-speed counter PV
is within a particular range.
Use the Range Comparison Condition Met Flags to determine whether the
high-speed counter PV is within a registered range.
Pausing Input Signal Counting (Gate Function)
If the High-speed Counter Gate Bit is turned ON, the corresponding high-
speed counter will not count even if pulse inputs are received and the counter
PV will be maintained at its current value. Bits A53108 to A53111 are the
High-speed Counter Gate Bits for high-speed counters 0 to 3.
Target value 1
Target value 2
Target value 1
Target value 2
Match not recognized.
Match
Match
Match
No. 255
No. 000
No. 000
No. 255
High-speed counter PV
Comparison is executed
without regard to the
order of the ranges in
the table.
Upper limit 1
Lower limit 1
Upper limit 2
Lower limit 2
Interrupt task that is started.
Time
Comparison table
Upper limit 1
Lower limit 1
Interrupt task = 000
Upper limit 2
Lower limit 2
Interrupt task = 255
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...