422
Analog I/O Units
Section 7-4
Reading Converted Analog Input Values
The ladder program can be used to read the memory area words where the
converted values are stored. Values are output to the next two words (m + 1,
m + 2) following the last input word (m) allocated to the CPU Unit or previous
Expansion Unit or Expansion I/O Unit.
Writing Analog Output Set Values
The ladder program can be used to write data to the memory area where the
set value is stored. The output word will be “n+1,” where “n” is the last output
word allocated to the CPU Unit or previous Expansion Unit or Expansion I/O
Unit.
Startup Operation
After power is turned ON, it will require two cycle times plus approx. 50 ms
before the first data is converted. The following instructions can be placed at
the beginning of the program to delay reading converted data from analog
inputs until conversion is actually possible.
Analog input data will be 0000 until initial processing has been completed.
Analog output data will be 0 V or 0 mA until the range code has been written.
After the range code has been written, the analog output data will be 0 V or
0 mA if the range is 0 to 10 V,
−
10 to 10 V, or 0 to 20 mA, or it will be 1 V or
4 mA if the range is 1 to 5 V or 4 to 20 mA.
Handling Unit Errors
• When an error occurs in the Analog I/O Unit, analog input data will be
0000 and 0 V or 0 mA will be output as the analog output.
If a CPU error or an I/O bus error (fatal errors) occurs at the CPU Unit and
the analog output is set to 1 to 5 V or 4 to 20 mA, 0 V or 0 mA will be out-
put. For any other fatal errors at the CPU Unit, 1 V or 4 mA will be output.
• CPM1A Expansion Unit/Expansion I/O Unit errors are output to bits 0 to 6
of word A436. The bits are allocated from A436.00 in order starting from
the Unit nearest the CPU Unit. Use these flags in the program when it is
necessary to detect errors.
Programming Example
This programming example uses these ranges:
Analog input 0: 0 to 10 V
Analog input 1: 4 to 20 mA
Analog output: 0 to 10 V
MOV(021)
2
D0
Always ON Flag
P_On
T5
#0002
T5
TIM 5 will start as soon as power turns ON.
After 0.1 to 0.2 s (100 to 200 ms), the input
for TIM 5 will turn ON, and the converted
data from analog input 0 that is stored in
word 2 will be transferred to D00000.
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...