557
Auxiliary Area Allocations by Address
Appendix D
A527
A527.00
to
A527.07
Online Edit-
ing Disable
Bit Validator
The Online Editing Disable Bit
(A527.09) is valid only when this byte
contains 5A.
To disable online editing from the
CX-Programmer, set this byte to 5A
and turn ON A527.09.
(Online editing refers to changing or
adding to the program while the PLC
is operating in MONITOR mode.)
5A:
A527.09
enabled
Other value:
A527.09 dis-
abled
Retained
Cleared
---
A527.09
A527.09 Online Edit-
ing Disable
Bit
Turn this bit ON to disable online
editing. The setting of this bit is valid
only when A527.00 to A527.07 have
been set to 5A.
ON: Disabled
OFF: Not dis-
abled
Retained
Cleared
---
A527.00
to
A527.07
A528
A528.00
to
A528.07
Serial Port 2
Error Flags
These flags indicate what kind of
error has occurred at the serial port
2; they are automatically turned OFF
when the serial port 2 is restarted.
(These flags are not valid in periph-
eral bus mode and only bit 5 is valid
in NT Link mode.)
PLC Link Polling Unit:
Bit 05: ON for timeout error.
PLC Link Polled Unit:
Bit 03: ON for framing error.
Bit 04: ON for overrun error.
Bit 05: ON for timeout error.
These bits can be cleared by the CX-
Programmer.
Bits 00 and 01:
Not used.
Bit 02: ON for
parity error.
Bit 03: ON for
framing error.
Bit 04: ON for
overrun error.
Bit 05: ON for
timeout error.
Bits 06 and 07:
Not used.
---
---
---
---
A528.08
to
A528.15
Serial Port 1
Error Code
These flags indicate what kind of
error has occurred at the serial port
1; they are automatically turned OFF
when the serial port 1 is restarted.
(These flags are not valid in periph-
eral bus mode and only bit 5 is valid
in NT Link mode.)
PLC Link Polling Unit:
Bit 13: ON for timeout error.
PLC Link Polled Unit:
Bit 11: ON for framing error.
Bit 12: ON for overrun error.
Bit 13: ON for timeout error.
These bits can be cleared by the CX-
Programmer.
Bits 08 and 09:
Not used.
Bit 10: ON for
parity error.
Bit 11: ON for
framing error.
Bit 12: ON for
overrun error.
Bit 13: ON for
timeout error.
Bits 14 and 15:
Not used.
---
---
---
---
A529
All
FAL/FALS
Number for
System
Error Simu-
lation
Set a dummy FAL/FALS number to
use to simulate the system error
using FAL(006) or FALS(007).
When FAL(006) or FALS(007) is exe-
cuted and the number in A529 is the
same as the one specified in the
operand of the instruction, the sys-
tem error given in the operand of the
instruction will be generated instead
of a user-defined error.
0001 to 01FF
hex: FAL/FALS
numbers 1 to
511
0000 or 0200
to FFFF hex:
No FAL/FALS
number for sys-
tem error simu-
lation. (No error
will be gener-
ated.)
Retained
Cleared
---
---
A531 A531.00 High-speed
Counter 0
Reset Bit
When the reset method is set to
Phase-Z Software reset, the
corresponding high-speed counter's
PV will be reset if the phase-Z signal
is received while this bit is ON.
When the reset method is set to Soft-
ware reset, the corresponding high-
speed counter's PV will be reset in
the cycle when this bit turns ON.
---
Retained
Cleared
---
---
A531.01 High-speed
Counter 1
Reset Bit
---
Retained
Cleared
---
---
A531.02 High-speed
Counter 2
Reset Bit
---
Retained
Cleared
---
---
A531.03 High-speed
Counter 3
Reset Bit
---
Retained
Cleared
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...