211
High-speed Counters
Section 5-2
5-2-3
Procedure
Select high-speed counter 0 to 3.
Select the pulse input method, reset
method, and counting range.
Select the kind of interrupt (if any).
Wire inputs.
PLC Setup settings
Ladder program
•
Pulse input methods: Differential phase (4x), Pulse +
direction, Up/Down, or Increment
•
Reset methods: Phase-Z + Software reset, Software
reset, Phase-Z + Software reset (continuing comparing),
Software reset (continuing comparing)
•
Counting ranges: Linear mode or Ring mode
•
Enable/disable interrupts
•
Target value comparison interrupt
•
Range comparison interrupt
•
Connect to the terminals (24 VDC input or line-
driver)
•
High-speed Counters 0 to 3 Enable/Disable:
•
High-speed Counters 0 to 3Pulse Input Mode:
Differential phase (4x)
Pulse + direction
Up/Down
Increment
•
High-speed Counters 0 to 3 Reset Method:
Phase-Z + Software reset, Software reset, Phase-Z + Software
reset (continuing comparing), Software reset (continuing
comparing)
•
High-speed Counters 0 to 3 Counting Mode:
Linear mode
Ring mode
•
Program the interrupt task (with any interrupt number between 0
and 255) to be executed when using a target value comparison
or range comparison interrupts.
•
Register a target value comparison table and start the
comparison.
•
Register a range comparison table and start the comparison.
•
Register a target value comparison table without starting the
comparison.
•
Register a range comparison table without starting the
comparison.
•
Change the counter PV.
•
Start comparison with the registered target value comparison
table or range comparison table.
•
Read the high-speed counter PVs, read the status of the high-
speed counter comparison operation, or read the range-
comparison results.
•
Turn ON the High-speed Counter Gate Bit to stop counting input
pulses.
•
High-speed counters 0 to 3 on X/XA CPU Units and high-speed
counters 2 and 3 on Y CPU Units: 24 VDC input, Response
frequency: 50 kHz for single-phase, 100 kHz for differential phase
•
High-speed counters on Y CPU Units: Line-driver input, Response
frequency: 500 kHz for single-phase, 1 MHz for differential phase
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...