468
Troubleshooting
Section 9-2
■
Reference Information
I/O Bus Errors
An I/O bus error occurs in data transfer between the CPU Units and Units
connected to the I/O bus. Cycle the power supply. If operation is not restored
when the power supply has been cycled, turn OFF the power supply and
check that connections are proper and that there is no damage.
■
Reference Information
Duplicate Number Error
A duplicate unit number error occurs for CJ-series Units. Turn OFF the power
supply and make sure the same unit number is not set for more than one Unit.
Error flag
Memory Error Flag, A401.15
Error code (A400)
80F1
Error information
Memory Error Location, A403
Seven-segment
display
Probable cause and possible remedy
8.0.
→
c.a.
→
0.a.
→
0.a.
→
I/O bus error for CPM1A Units
An error has occurred in data transfer with a CPM1A Expan-
sion Unit or Expansion I/O Unit. Check the condition of the
connection cables.
8.0.
→
c.f.
→
0.f.
→
0.f.
→
I/O bus error for CJ-series Units, error location unknown
An error has occurred in data transfer for CJ-series Units, but
the error location is not known. Check the connections
between the CPU Unit, CJ Unit Adapter, and CJ-series Units.
8.0.
→
c.e.
→
0.e.
→
0.e.
→
I/O bus error for CJ-series Units, no End Cover
No End Cover has been installed for CJ-series Units. Properly
install the End Cover.
8.0.
→
c.0.
→ →
0.0.
→
0.0.
→
First CJ-
series Unit
An error has occurred in data transfer for
CJ-series Units (first Unit or second Unit).
Check that there is no damage to the rele-
vant Unit. Replace the Unit if required.
→
0.0.
→
0.1.
→
Second CJ-
series Unit
Error flag
I/O Bus Error Flag, A401.14
Error code (A400)
80C0, 80CA, 80CE, 80CF
Error information
I/O bus error details, A404
8.0.
c.0.
→
→
→
I/O bus error location
8.0.
→
e.9.
→
→
→
Duplicate Unit numbers
Seven-segment display
Probable cause and possible remedy
8.0.
→
e.9.
→ →
0.0.
→
0.1.
→
The same number has been set for more than one CPU
Bus Unit. Check the unit number settings and eliminate
the duplication.
→
8.0.
→
0.1.
→
The same number has been set for more than one Spe-
cial I/O Unit. Check the unit number settings and elimi-
nate the duplication.
Содержание CP1H-CPU - 05-2006
Страница 1: ...OPERATION MANUAL CP1H CPU Unit SYSMAC CP Series CP1H X40D CP1H XA40D CP1H Y20DT D Cat No W450 E1 02...
Страница 2: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised May 2006...
Страница 3: ...iv...
Страница 11: ...xii TABLE OF CONTENTS...
Страница 15: ...xvi...
Страница 19: ...xx...
Страница 31: ...xxxii Conformance to EC Directives 6...
Страница 71: ...40 Function Blocks Section 1 5...
Страница 133: ...102 Computing the Cycle Time Section 2 7...
Страница 169: ...138 CPM1A Expansion I O Unit Wiring Section 3 6...
Страница 411: ...380 Clock Section 6 8...
Страница 519: ...488 Replacing User serviceable Parts Section 10 2...
Страница 527: ...496 Standard Models Appendix A...
Страница 535: ...504 Dimensions Diagrams Appendix B...
Страница 628: ...597 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 629: ...598 Connections to Serial Communications Option Boards Appendix F...
Страница 659: ...628 PLC Setup Appendix G...
Страница 665: ...634 Index work words 159 write protection 370...
Страница 667: ...636 Revision History...