255
Pulse Outputs
Section 5-3
When the Origin Proximity Input Signal is received, the motor will begin decel-
erating from the origin search high speed to the origin search proximity speed.
In this operating mode, the motor will stop at the Origin Input Signal after
deceleration is completed.
1
1
0
0
Approx. 20 to 30 ms
Origin Input Signal
(Phase-Z signal)
Pulse output
Error Counter Reset
Signal