If your system does not have onboard keymanager, NSE or NVE configured, complete the steps in this
section.
6. From the LOADER prompt, enter the
boot_ontap
command.
If you see…
Then…
The login prompt
Go to the next Step.
Waiting for giveback…
a. Log into the partner node.
b. Confirm the target node is ready for giveback with the
storage
failover show
command.
7. Connect the console cable to the partner node.
8. Give back the node using the
storage failover giveback -fromnode local
command.
9. At the cluster prompt, check the logical interfaces with the
net int -is-home false
command.
If any interfaces are listed as "false", revert those interfaces back to their home port using the
net int
revert
command.
10. Move the console cable to the repaired node and run the
version -v
command to check the ONTAP
versions.
11. Restore automatic giveback if you disabled it by using the
storage failover modify -node local
-auto-giveback true
command.
Restore OKM, NSE, and NVE as needed - FAS500f
Once environment variables are checked, you must complete steps specific to systems
that have Onboard Key Manager (OKM), NetApp Storage Encryption (NSE) or NetApp
Volume Encryption (NVE) enabled.
1. Determine which section you should use to restore your OKM, NSE, or NVE configurations: If NSE or NVE
are enabled along with Onboard Key Manager you must restore settings you captured at the beginning of
this procedure.
◦
If NSE or NVE are enabled and Onboard Key Manager is enabled, go to
Onboard Key Manager is enabled
◦
If NSE or NVE are enabled for ONTAP 9.6, go to
Restore NSE/NVE on systems running ONTAP 9.6
Restore NVE or NSE when Onboard Key Manager is enabled
Steps
1. Connect the console cable to the target node.
2. Use the
boot_ontap
command at the LOADER prompt to boot the node.
3. Check the console output:
1118
Содержание AFF A700
Страница 4: ...AFF and FAS System Documentation 1...
Страница 208: ...3 Close the controller module cover and tighten the thumbscrew 205...
Страница 248: ...2 Close the controller module cover and tighten the thumbscrew 245...
Страница 308: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 305...
Страница 381: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 378...
Страница 437: ...1 Locate the DIMMs on your controller module 434...
Страница 601: ...Cabling SAS shelves in FAS9000 AFF A700 and ASA AFF A700 ONTAP 9 8 and later Cabling SAS storage ONTAP 9 8 and later 598...
Страница 605: ...602...
Страница 1117: ...3 Close the controller module cover and tighten the thumbscrew 1114...
Страница 1157: ...2 Close the controller module cover and tighten the thumbscrew 1154...
Страница 1228: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 1225...
Страница 1300: ...Power supply Cam handle release latch Power and Fault LEDs Cam handle 1297...
Страница 1462: ...Installing SuperRail to round hole four post rack 1459...
Страница 1602: ...1599...
Страница 1630: ...1627...
Страница 1634: ...Orange ring on horizontal bracket Cable chain 1631...
Страница 1637: ...b Raise the drive handle to vertical c Use the handle to lift the drive from the drive drawer 1634...
Страница 1643: ...Callout Cable chain Connector Connects to Left Vertical Midplane Left Horizontal Drive drawer 1640...
Страница 1645: ...Guide rail 1642...
Страница 1648: ...Tab that you press to release the fan module handle 5 Use the fan module handle to pull the fan module out of the shelf 1645...
Страница 1669: ...Attention LED light on 1666...