245
-
UPS status after blade shutdown
Select either of "Put UPS running on battery to sleep" or "Put all UPS to temporarily
sleep" when the EM card shuts down the CPU blade because the number of healthy UPSs
has decreased due to input power lost.
The UPS is put in temporarily sleep state for 6 minutes.
The default setting is "Put UPS running on battery to sleep". You need not to change in
usual case.
NOTE:
While the Web console of the UPS is open or the command
line console of the UPS is connected, the sleep feature is unavailable.
UPS Sleep Delay
Specify the time until the UPS actually enters into sleep state after the sleep command is
issued to UPS, in the unit of second. Available value depends on the UPS model. See the
table below. The default setting is 90 seconds.
If an illegal value is specified for the relevant UPS, the longest time allowed for that UPS
is set.Ex.) If "120" is specified for N8142-29, "630" seconds is set.
UPS model
Allowable value (seconds)
N8142-11B
20
180
300
600
N8142-23A
0
90
180
270
360
450
540
630
N8142-24A
0
20
60
120
240
480
720
960
N8142-25/25A
0
20
60
120
240
480
720
960
N8142-29
0
90
180
270
360
450
540
630
N8142-31
0
90
180
270
360
450
540
630
N8142-35
0
20
60
120
240
480
720
960
N8142-38
0
90
180
270
360
450
540
600
N8142-42
0
90
180
270
360
450
540
600
IMPORTANT:
UPS Sleep Delay can not be set from the EM Card for
N8142-38 and N8142-42. It needs to be set using the web console of
the SNMP card. See “Setting UPS Sleep Delay on N8142-38 and
N8142-42” below for instructions.
Setting UPS Sleep Delay on N8142-38 and N8142-42
Open the Status screen of the EM Card web console and click the HTTP button on the list
of UPS.
Содержание N8405-019
Страница 4: ... ii ...
Страница 6: ... iv ...
Страница 8: ... vi ...
Страница 10: ... viii ...
Страница 12: ... x ...
Страница 19: ... xvii Collection using Command Line Console 352 Collection using NEC ESMPRO Manager 352 Others 353 ...
Страница 20: ......
Страница 231: ... 211 N8403 099 F N8403 100 F ...
Страница 233: ... 213 Figure 1 Example of conflict of vIO information occurred when backing up and restoring the configuration ...
Страница 235: ... 215 Figure 2 Example of conflict of vIO information occurred when restoring the configuration to other Blade Enclosure ...
Страница 237: ... 217 Figure 3 Example of conflict of vIO information occurred when initializing the EM card ...
Страница 253: ... 233 NEC SigmaSystemCenter Enable or disable access from NEC SigmaSystemCenter The default is Disable ...
Страница 266: ... 246 Login to the web console of the UPS The default username and password is Username apc Password apc ...
Страница 267: ... 247 After login click Outlet Groups in the Configuration Click on the Oulet Group to be configured ...