Note:
The OPEN side limit signal and CLOSE side must use both by the pair. Either alone
cannot be used. Select both the OPEN side limit signal and the CLOSE side turning of
when not using this function.
7.4.5
Original point sensor signal (ORIGIN SENSOR)
When the original point sensor is used for the original point position detection at the
gate, an input signal efective state of original point sensor is set.
The signal of original point sensor is selectable from [SHORT], [OPEN] or [OFF].
The default has selected as [SHORT].
7.4.6
Ready signal (READY FOR OPERATION)
An input efective state of ready signal output from the servo ampliier is set. [SV.ERR RD]
lights when the ready signal becomes inefective condition.
Ready signal is selectable from [SHORT] or [OPEN].
The default has set as [SHORT].
CAUTION
Warning of personal injury and damage to property.
The limit signal for OPEN side, the limit signal for CLOSE side and the original point
sensor signal are turned of.
Make sure to use a protection device for the servomotor operation in the system.
7.5 Calibration of manual speed (MANUAL SPEED CALIB.)
The speed calibration when the gate is operated in manual is executed.
CAUTION
Damage to the system or malfunctions are possible.
Set each parameter after conirming the speciication of this unit and the servo
ampliier and the servo motor used enough.
1. Select [CLOSE LIMIT SENSOR] in the screen of input efective state.
2. Select the input efective state of CLOSE side limit signal.
3. Tap [OK].
1. Select [ORIGIN SENSOR] in the screen of input efective state.
2. Select the input efective state of the signal of original point sensor.
3. Tap [OK].
1. Select [READY FOR OPERATION] in the screen of input efective state.
2. Select the level of the ready signal from [SHORT] or [OPEN].
3. Tap [OK].
7 Servo calibration
Weight Controller CSD-918
Minebea Intec
EN-61