Item name
Command name
Com-
mand
Number Return command setting value
SPAN POINT mV/V regist-
ration (fourth decimal pla-
ce)
75
07
–0.000 1 to 3.100 0 mV/V (Unit: 0.0001
mV/V)
DECIMAL POINT
75
11
1: [0]; 2:[0.0]; 3: [0.00]; 4: [0.000]; 5:
[0.0000]
UNIT
75
12
1: [None]; 2: [g]; 3: [kg]; 4: [t]; 5: [lb]; 6: [N];
7:[kN]
BRIDGE POWER SUPPLY
75
13
1: [12 V]; 2: [6 V]; 3: [3V]
OL DISPLAY CONDITION
75
14
1: [+9 D]; 2: [≥110%]; 3: [–20 D ~ 9 D]
ADJ. (calibrate) BRAV. AC-
CELERATION
75
21
1: DISTRICT No.; 2: GRAVITY ACCELERATI-
ON
CALIB. PLACE No.
75
22
01 to 16
OPERATION PLACE No.
75
23
01 to 16
CALIB. PLACE G.A.
75
24
9.000 to 9.999 (Unit: 0.001)
OPERATION PLACE G.A.
75
25
9.000 to 9.999 (Unit: 0.001)
ZERO POINT mV/V (ifth
decimal place)
75
26
–2.50000 to 2.50000 mV/V (Unit: 0.00001
mV/V)
Span point mV/V registra-
tion (ifth decimal place)
75
27
–0.00001 to 3.10000 mV/V (Unit: 0.00001
mV/V)
Rated motor rotation
speed
A0
01
500 to 10 000 r/min
(Unit: r/min)
Maximum input pulse fre-
quency
A0
02
20 to 8 000 000 pps (Unit: pps)
Input pulse per motor ro-
tation
A0
03
20 to (8 000 000/(rated motor rotation/
60)) pulses (Unit: pulse)
Input pulse per rotation
A0
04
20 to 1 073 741 824 pulses (Unit: pulse)
Command pulse method
A0
05
1: [1PULSE METHOD]; 2: [2PULSE
METHOD]; 3: [2PHASE PULSE METHOD]
Command pulse polarity
A0
06
1: [CW]; 2: [CCW]
Command pulse logic
A0
07
1: [POSITIVE LOGIC]; 2: [NEGATIVE LOGIC]
Open side software limit
A5
01
1: [ EFFECTIVE]; 0: [INVALID]
OPEN side software limit
setting
A5
03
1.000 to 100.000 %
(Unit: 0.001 %)
CLOSE side software limit A5
04
1: [ EFFECTIVE]; 0: [INVALID]
CLOSE side software limit
setting
A5
06
–1.000 to –100.000 % (Unit: 0.001 %)
Servo calibrati-
on
Deviation software limit
A5
07
1: [ EFFECTIVE]; 0: [INVALID]
Weight Controller CSD-918
17 Options
EN-176
Minebea Intec
Содержание CSD-918 Series