10. Object Dictionary
10-46
ent
UDINT
0 to 2147483647
100000
pulse
RW
No
Always
Yes
0x2028
Load Encoder Following Error Reset
ALL
Variable
Type
Setting Range
Initial Value
Unit
Accessi
bility
PDO
Assignm
ent
Variable
Attribute
Savin
g
UDINT
0 to 10000
10
Rev
RW
No
Always
Yes
This sets the position error level for the external encoder and the reset range for the error position value.
Based on the 0x2027 (External Encoder Following Error Window) settings, the AL-54 (Encoder2 POS
difference) level can be adjusted. For a system where a slip occurs, the 0x2028 (External Encoder
Following Error Reset) settings can be used to set the normal slip range for the following error value.
0x2029
External Encoder Z found
ALL
Variable
Type
Setting Range
Initial
Value
Unit
Accessi
bility
PDO
Assignm
ent
Variable
Attribute
Savin
g