9. Full-Closed Control
9-4
C. Entering load encoder information
0x202B
Load Encoder Configuration
ALL
Variable
Type
Setting Range
Initial Value
Unit
Accessi
bility
PDO
Assignm
ent
Variable
Attribute
Savin
g
UINT
0 to 65535
13
-
RW
No
Power
cycling
Yes
This sets the second encoder, which is attached to the load side.
The settings below change depending on the setting of the encoder type 1. Do not set the reserved
bit.
Bits
Description (if encoder type is quadrature)
3~0
Debounce filter settings
Settings
Cutoff Frequency
0
No Filter
1
5.000MHz
2
3.330MHz
3
2.500MHz
4
2.000MHz
5
1.667MHz
6
1.429MHz
7
1.250MHz
8
1.000MHz
9
0.833MHz
10
0.714MHz
31~4
Reserved
Bits
Description (if encoder type is SSI)
0-7
Number of bits for data
8
Coding(0:binary, 1:gray)
9
Whether to ignore the first bit (0: one start bit, 1: two start bits)
10-11
Reserved
12-15
Clock rate
(0:656.25kHz, 1:1.3125Mhz, 2:2.625Mhz)
16-31
Reserved