5. Drive Application Functions
5-26
5.5.2
Position Control Signals
As shown in the figure below, if the following error value (i.e., the difference between the position
command value input by the upper level controller and the position feedback value) is below the
INPOS1 output range (0x2401) and is maintained for the INPOS1 output time (0x2402), the INPOS1
(Positioning completed 1) signal is output. However, the signal is output only when the position
command is not renewed.
Here, if the following error value goes below the INPOS2 output range (0x2403), the INPOS2
(Positioning completed 2) signal is output regardless of whether or not the position command has been
renewed.
Speed
Time
Command
Feedback
INPOS1 (for output time = 0)
Position
Error
Time
INPOS2
Position command
renewal start time
Position
command
renewal end time
INPOS1/2
output
range
Related Objects
Index
Sub
Index
Name
Variable
Type
Accessibility
PDO
Assignment
Unit
0x2401
-
INPOS1 Ouput Range
UINT
RW
Yes
UU
0x2402
-
INPOS1 Ouput Time
UINT
RW
Yes
ms
0x2403
-
INPOS2 Ouput Range
UINT
RW
Yes
UU