13. Test Drive
13-6
9
Switch the EtherCAT communication state from SafeOP to OP, enabling
MailBox Communication and Process Data Communication.
Click the Generate Mappings icon on the menu bar.
Map the images defined in NC Task and I/O Device.
Click the Check Configuration icon on the menu bar.
Check if the currently set configuration is valid.
Click the Activate Configuration icon on the menu bar.
Save Project Configuration in Windows Registry.
10
Verify if the EtherCAT communication state has switched from SafeOP to OP.
Verify if the states of the servo drive panel monitor and the I/O device
(servo drive) of the TwinCAT system are in the online state as shown in the
figure below.
Check the panel monitor status.
Check the communication LED.
The Link/Activity LED is flickering.
The RUN LED is on.
Check the online state of the I/O device of the TwinCAT system.
In the I/O-Configuration tree of the workspace, click the servo drive, and
then click the Online tab to check if Current State and Requested State are
in the OP state.