Example configurations
Leuze electronic GmbH + Co. KG
CML 730i
169
15.4.2 Configuration of blanking areas via IO-Link interface
Perform blanking area activation and deactivation.
Example: automatic blanking of two areas during teaching
In the background, the values of objects INDEX 76 sub-index 3 et seq. are calculated and stored in non-
volatile memory. Upon successful teach completion, all other objects of index 76 are stored in non-volatile
memory if index 79, sub-index 2 is set to value 0 = non-volatile storage of teach values.
Example: Deactivation/resetting of auto blanking
15.4.3 Configuration of blanking areas via CANopen interface
Perform blanking area activation and deactivation.
Example: automatic blanking of two areas during teaching
In the background, the values of objects 0x2104 sub 04 and 0x2104 sub 05 as well as 0x2104 sub 07 and
0x2104 sub 08 are calculated and stored in non-volatile memory. Following a successful teach, all other
0x2104 objects are stored in non-volatile memory if 0x2103 sub 02 is set to value 0 = non-volatile storage
of teach values.
Example: Deactivation/resetting of auto blanking
Blanking settings
Parameter
Number of auto blanking areas
:
= 0
No blanking areas permitted
Parameter
Auto blanking (during teaching)
:
= 0
Automatic blanking area configuration not active
Blanking settings
Parameter
Function for blanking area/logical value
for blanking area 1
:
= 0
No beams blanked
Parameter Function for blanking area/logical value
for blanking area 2:
= 0
No beams blanked
System commands
Parameter
Teach command
:
= 1
Execute teach command
Blanking settings
(group 8)
Index 76, bit offset 200:
= 2
Two blanking areas permitted
Index 76, bit offset 192:
= 1
Automatic blanking-area configuration active
System commands
(group 1)
Index 2
= 162
Execute teach
Blanking settings
(group 8)
Index 76, bit offset 200:
= 0
No blanking areas permitted
Index 76, bit offset 192:
= 0
Automatic blanking area configuration not active
Blanking settings
(group 8)
Index 76, bit offset 176:
= 0
No beams blanked
Index 76, bit offset 176:
= 0
No beams blanked
System commands
(group 1)
Index 2:
= 162
Execute teach
Blanking settings
(module 6)
Index 0x2104 sub 01:
= 2
Two blanking areas permitted
Index 0x2104 sub 02:
= 1
Automatic blanking-area configuration active
Commands
(module 9)
Index 0x2200 sub 01:
= 3
Execute teach
Blanking settings
(module 6)
Index 0x2104 sub 01:
= 0
No blanking areas permitted
Index 0x2104 sub 02:
= 0
Automatic blanking area configuration not active
Blanking settings
(module 6)
Index 0x2104 sub 03:
= 0
No beams blanked
Index 0x2104 sub 03:
= 0
No beams blanked
Commands
(module 9)
Index 0x2200 sub 01:
= 3
Execute teach