Starting up the device - PROFINET interface
Leuze electronic GmbH + Co. KG
CML 730i
143
0x03
0x11
0x0000
Trigger com
-
mand
0x00
0x11
0x0100
Receiver received
command.
0x04
0x11
0x0000
0x03
0x11
0x1000
Receiver suc
-
cessfully executed
command and sent a
confirmation (ACK).
0x04
0x12
0x0000
0x00
0x12
0x0100
Receiver (Rx) recei
-
ved new command.
0x04
0x12
0x0000
Trigger next
command
0x04
0x12
0x2000
Receiver executed
command and sent a
rejection (NACK)
because no suc
-
cessful teaching had
yet been performed.
0x00
0x12
0x0000
Reset trigger
0x00
0x00
0x0000
Reset.
0x00
0x15
0x00A5
Output data
Input data
"0x" designates the corresponding entry as hexadecimal number. The actual entry consists only
of the following digits and is also only to be entered as such.
The trigger echo is not accepted until after the receiver answer (Rx answer) is received. A trigger
byte change is ignored during "Answer" state 0x0100.
For controls of type Siemens S7, the lowbyte/highbyte sequence is to be taken into account for
WORD and DWORD!
With these controls, the addressing sequence in single-byte output shows the highbyte first and
then the lowbyte.