Starting up the device - Basic configuration
Leuze electronic GmbH + Co. KG
CML 730i
70
The structure of the configuration in the receiver control panel menu is as follows:
Select Main Settings > Operation Settings > Function Reserve
For the switching threshold, enter a value between 10% (lowest sensitivity) and 98% (highest sensiti
-
vity).
8.5
Extended configurations on the receiver control panel menu
8.5.1 Define digital inputs/outputs
The digital IO configurations (IO Pin 2, IO Pin 5 and IO Pin 6) are used to configure the parameters for the
switching outputs:
• IO function: trigger input, teach input, command output, warning output, trigger output or validation
output
• Inversion
• Area logic
• Start beam
• End beam
The sensitivity levels (e.g., high function reserve for stable operation, medium function reserve
and low function reserve) are configured ex works with “high function reserve for stable
operation”. The “low function reserve” configuration enables the detection of partially transparent
objects.
The switching threshold can be set for optimum operation for the detection of transparent objects
in the “Transparent” configuration.
Level 0
Level 1
Level 2
Description
Main Settings
Commands
Teach
Reset
Factory settings
Operation Settings
Filter depth
Beam mode
Function reserve
High
Medium
Low
Transparent
Switching threshold
NOTICE
Recommended switching threshold for transparent objects!
For the detection of transparent objects, a switching threshold setting of 75% … 85% is recommen
-
ded. Factory setting: 75%.
The adjustment options
Nominal value
,
Transmitting power
and
Receiver sensitivity
have no
function in the function reserve modes
High
,
Medium
,
Low
and
Transparent
. These settings are
only effective when configuring the function reserve modes
Target function reserve
and
Tx/
Rx power
.
It is not mandatory that extended configurations be performed on the receiver control panel menu
in order to start up a light curtain.