Example configurations
Leuze electronic GmbH + Co. KG
CML 730i
167
15.3.1 Configuration of hole recognition via IO-Link interface
For hole recognition for web material map hole indication to output pin 2.
15.3.2 Configuration of hole recognition via CANopen interface
For hole recognition for web material map hole indication to output pin 2.
15.3.3 Configuration of hole recognition via PROFIBUS interface
For hole recognition for web material map hole indication to output pin 2.
Digital Output 2 Settings
Area mapping 32 … 1
(OR combination)
0b 0000 0000 0000 0000 0000 0000 0000 0001
Configuration of area 01
(group 14)
Index 00, bit offset 104:
= 1
Area 01 active
Index 100, bit offset 96:
= 0
Light switching
Index 100, bit offset 80:
= 65534
Start beam of the area dynamic: on 65534 (start beam = FIB)
Index 100, bit offset 64:
= 65532
End beam of the area dynamic: on 65532 (start beam = LIB)
Index 100, bit offset 48:
= 1
Number of active beams for area ON
Index 100, bit offset 32:
= 0
Number of active beams for area OFF
Digital IO Pin 2 Settings
(group 10)
Index 80, bit offset 24:
= 0
Pin 2 as output
Index 80, bit offset 16:
= 1
Switching behavior inverted
Index 80, bit offset 0:
= 1
Switching output area 32 … 1
Index 84, bit offset 0:
= 1
Bit mapping of area 01 to pin 2
Configuration of area 01
(module 8)
Index 0x2170 sub 01:
= 1
Area 01 active)
Index 0x2170 sub 02:
= 0
(Light switching
Index 0x2170 sub 03:
= 65534
Start beam of the area dynamic: on 65534 (start beam = FIB)
Index 0x2170 sub 04:
= 65532
End beam of the area dynamic: on 65532 (start beam = LIB)
Index 0x2170 sub 05:
= 1
Number of active beams for area ON
Index 0x2170 sub 06:
= 0
Number of active beams for area OFF
Switching level of inputs/outputs
(module 7)
Index 0x2151 sub 01:
= 0
Pin 2 as output
Index 0x2151 sub 03:
= 1
Switching behavior inverted
Index 0x2151 sub 04:
= 1
Switching output area 32 … 1
Index 0x2155 sub 03:
= 1
Bit mapping of area 01 to pin 2
Area settings
(module 18)
Parameter
Area configuration
:
= 1
Area 01 selected
Parameter
Area
:
= 1
Area 01 active
Parameter
Logical behavior of the area
:
= 0
0: Normal - light switching
Parameter
Start beam of the area
:
= 65534
Start beam of the area dynamic: on 65534
(start beam = FIB)
Parameter
End beam of the area
:
= 65532
End beam of the area dynamic: on 65532
(start beam = LIB)
Parameter
Number of active beams → ON
:
= 1
Number of active beams for area ON
Parameter
Number of active beams → OFF
:
= 0
Number of active beams for area OFF