Id.-Nr.: 1556.212.1-07
Connections and wiring
Description
LTI Mat. No.
Designation
RJ45 connector
62631
Modular 8-pole plug, shielded
Plug protection cap
63054
PVC cover for modular plug,
blue
The cable shielding must be connected over a wide area with the shield cover of the
plug. An additional connection of the shield and the ground is not necessary.
Cable length
A 100 Mbit/s Ethernet transmission is specified up to a maximum of 50 m (guaran-
teed) according to IEEE 802.3. The maximum possible transmission distance can be
shorter in an EMC-interfered industrial environment.
Minimum bend radius
During the installation: 60 mm.
For installed cable: 50 mm.
5.1.6
Graphic interface
Cable type
A cable according to the following specifications must be used to connect a panel to
the controller: Twisted pair and shielded data cables;
Type:
UL20276 (28 AWGx1-
PAIR + AL - FOIL + MYLAR + DRAIR) x 5C + 18 AWG x 4C + AL - FOIL + BRAID;
Black PVC Jacket.
Plug type
he following preassembled cables (with 15-pole DSUB plug) can be purchased from
LTI.
Designation
Length
Note
LAXW 044-050
5 m
Connection between panel
and MO CM
LAXW 041-050
5 m
Connection between panel
and LACP 26x
Minimum bend radius
During installation: 60 mm
For installed cable: 50 mm
Information
For information about the operating panels and CPU modules, please refer
to the operation manual of the respective device.
5.1.7
USB
The USB-interfaces are used to connect different media (e.g. for maintenance work).
They are, however, not suited for unmonitored continuous operation as the connec-
tion plug does not have a strain relief.
Information
The use of USB-enabled devices from the computer world may result in un-
expected system behavior or system failures, as these devices are not nor-
mally designed for operation in an environment with industrial interference.
Cable type
Shielded USB cable, twisted pair data cables with a surge impedance of 90 Ω ±15 %.
Plug type
Standard USB connector with fully conductive shell.
The cable shielding must be connected over a wide area with the shield cover of the
plug. An additional connection between the shield and the ground is not necessary.
Cable length
Max. 5 m.
5.2
Connecting the bus link module
The bus link module is connected to the control via the field bus interface.