24
Id.-Nr.: 1556.212 .1-07
Connections and wiring
Minimum bend radius
During the installation: 60 mm.
For installed cable: 50 mm.
5.1.4
SSI interface
Cable type
The shielded connection was tested with the following cable type.
Type
Designation
Manufacturer
Article-No.
Hard-wired cable (oil-
resistant)
Etherline P-Cat
LAPP cable
2170297
Flexible cable (oil-re-
sistant)
Etherline P Flex 5e
LAPP cable
2170300
Flexible cable (not oil-
resistant)
"Silverline Gold" Cat.
7 patch cable, S/STP
4x2x0,14qmm
DRAKA multimedia
CNS796031
This (or a qualitatively equivalent) cable must be used for the connection.
Plug type
The following parts for the manufacturing of plug connections can be ordered from
LTI.
Description
LTI Mat. No.
Description
RJ45 connector
62631
Modular-Plug 8pol., shielded
Plug protection cap
63054
PVC cover for modular plug,
blue
The cable shielding must be connected plane with the shield cover of the plug. An
additional connection of the shield and the ground is not necessary.
Baud rate / maximum cable length
The baud rate can be set individually by software. The maximum possible baud rate
depends on the cable length.
The values specified in the table were determined by measurements with the follow-
ing equipment.
Baud rate
Max. cable length [m]
125 kBaud
125
250 kBaud
100
500 kBaud
75
1 MBaud
50
Information
We recommend dimensioning the SSI cable so that it is only as long as ab-
solutely necessary.
Minimum bend radius
For installed cable: 50 mm.
5.1.5
Ethernet, Gigabit-Ethernet, EtherCAT, PROFINET
Cable type
The shielded connection was tested with the following cable type.
Designation
Manufacturer
Article no.
"Silverline Gold" Cat. 7 patch
cable, S/STP 4x2x0,14 sqmm
DRAKA Multimedia
CNS796031
For the connection, this or a qualitatively equivalent cable must be used for the con-
nection (twisted pair and shielded data cables with a characteristic impedance of 100
Ω ±15%, ...).
Plug type
The following parts for the manufacturing of plug connections can be ordered from
LTI.