Goodrive20-EU Series VFD
Function parameters
-79-
Function
code
Name
Description
Default Modify
Setting range of P08.34: 0.00Hz
–P00.03
(the max. frequency)
P08.36
Amplitude
value for
frequency
arrival
detection
When the output frequency is among the below
or above range of the set frequency, the
multi-function digital output terminal will output
the signal of "frequency arrival", see the diagram
below for detailed information:
Y,
RO1, RO2
Output frequency
t
Setting
frequency
P08.36
t
P08.36
Setting
range:
0.00Hz
–P00.03 (the max.
frequency)
0.00Hz
○
P08.37
Energy
consumption
brake enable
This parameter is used to control the internal
braking unit.
0: Disabled
1: Enabled
Note:
It is only applicable to VFD models that are
built in braking units.
0
○
P08.38
Energy
consumption
brake
threshold
voltage
After setting the original bus voltage to brake the
energy, adjust the voltage appropriately to brake
the load. The factory changes with the voltage
level.
Setting range: 200.0
–2000.0V
In order to prevent customers set the value is too
large, it is recommended setting range:
Voltage
220V/230V
400V
460V
Range
375
–400V 685–750V 715–780V
For
220/230V
VFDs:
380.0V
○
For 400V
VFDs:
700.0V
For 460V
VFDs:
740.0V
P08.39
Cooling fan
running mode
0: Common running mode
1: Keeps running after being powered on
2: Runs when the VFD ramp frequency is no less
than 0 Hz and the VFD output current is no less
0
○
Содержание Goodrive20-EU VFD Series
Страница 1: ......
Страница 173: ...6 6 0 0 1 0 0 4 8 4...