Goodrive20-EU Series VFD
Function parameters
-43-
Function
code
Name
Description
Default Modify
P01.10
Stop brake
waiting time
output before starting the DC braking. After this
waiting time, the DC braking will be started so as
to prevent over-current fault caused by DC
braking at high speed.
DC braking current: the value of P01.11 is the
percentage of rated current of VFD. The bigger
the DC braking current is, the greater the braking
torque is.
DC braking time: the retention time of DC
braking. If the time is 0, the DC braking is invalid,
and the VFD will coast to stop.
P01.04
ACC
P1314
.
P0123
.
Constant
speed
In running
DEC
P0110
.
P1315
.
P01.12
P01.09
t
Setting range of P01.09: 0.00Hz
–P00.03
(the max. frequency)
Setting range of P01.10: 0.00
–50.00s
Setting range of P01.11: 0.0
–100.0% (rated
current peak of the VFD)
Setting range of P01.12: 0.00
–50.00s
0.00s
○
P01.11
Stop DC
braking current
0.0%
○
P01.12
Stop DC
braking time
0.00s
○
P01.13
FWD/REV
running
deadzone time
This function code indicates the transition time
specified in P01.14 during FWD/REV rotation
switching. See the following figure.
Output frequency
FWD
REV
T
Starting
frequency
Shift after the
zero frequency
Shift after the
starting frequency
Setting range: 0.0
–3600.0s
0.0s
○
P01.14
FWD/REV
switching mode
Set the threshold point of the VFD:
0: Switch at zero frequency
1
◎