Goodrive20-EU Series VFD
Function parameters
-42-
Function
code
Name
Description
Default Modify
fmax
Output frequency
t1
t2
T
1: S curve
The output frequency increases or decreases
progressively according to the S curve. The S
curve type is generally applied in elevators,
conveyors, and other application scenarios
where smoother start or stop is required.
Output frequency
t
t1
t2
t1
t2
t1=P01.06; t2=P01.07
P01.06
Acceleration
time of the
starting step of
S curve
Setting rage: 0.0
–50.0s
Note: Effective when P01.05 is 1
0.1s
◎
P01.07
Deceleration
time of the
ending step of
S curve
0.1s
◎
P01.08 Stop selection
0: Decelerate to stop: after the stop command
becomes valid, the VFD decelerates to reduce
the output frequency during the set time. When
the frequency decreases to 0Hz, the VFD stops.
1: Coast to stop: after the stop command
becomes valid, the VFD ceases the output
immediately. And the load coasts to stop at the
mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
while stop
Starting frequency of DC braking: start the DC
braking when running frequency reaches starting
frequency determined by P01.09.
Waiting time before DC braking: VFDs blocks the
0.00Hz
○