Goodrive20-EU Series VFD
Fault tracking
-111-
Fault
code
Fault type
Possible cause
Solutions
keypad.
Backup data in the keypad
again.
ETH1
[32] To-ground
short-circuit
fault 1
The output of the VFD is
short circuited to the
ground;
There is fault in the current
detection circuit;
There is a great difference
between the actual motor
power setting and the VFD
power.
Check if the connection of
the motor is normal or not;
Replace the hall;
Replace the main control
panel;
Reset motor parameters
and ensure those
parameters are correct;
Check whether motor
power parameters in P2
group are consistent with
the motor power actually
used.
ETH2
[33] To-ground
short-circuit
fault 2
dEu
[34] Speed
deviation
fault
Load is too heavy, or stall
occurred.
Check the load to ensure it
is proper, increase the
detection time.
Check whether control
parameters are set
properly.
STo
[35]
Mal-adjustment
fault
Control parameters of
synchronous motor are set
improperly.
The parameter gained
from autotuning is
inaccurate.
The VFD is not connected
to motor.
Check the load to ensure it
is proper.
Check whether control
parameters are set
correctly.
Increase maladjustment
detection time.
LL
[36] Electronic
underload fault
The VFD will report the
underload pre-alarm
according to the set value.
Check the load and the
underload pre-alarm point.
STO
[37] Safe torque
off
STO function operates
normally
STL1
[38] Channel H1
abnormal
Fault or internal hardware
circuit fault occurred to H1
channel
Replace STO switch; if
problem persists after
replacement, contact the
Содержание Goodrive20-EU VFD Series