Goodrive20-EU Series VFD
Function parameters
-35-
Function
code
Name
Description
Default Modify
P00.05
Lower limit of
running
frequency
The lower limit of the running frequency is that of
the output frequency of the VFD.
The VFD runs at the lower limit frequency if the
set frequency is lower than the lower limit.
Note:
Max.
output frequency ≥ upper limit
frequency ≥ lower limit frequency
Setting range: 0.00Hz
–P00.04 (upper limit of the
running frequency)
0.00Hz
◎
P00.06
A frequency
command
selection
Note:
A frequency and B frequency cannot set
as the same frequency reference method. The
frequency source can be set by P00.09.
0: Set via keypad digits
Modify the value of function code P00.10 (set the
frequency by keypad) to change the frequency
by the keypad.
1:
Set
via
AI1
(corresponding
keypad
potentiometer)
2: Set via AI2 (corresponding terminal AI2)
3: Set via AI3 (corresponding terminal AI3)
Set the frequency by analog input terminals.
Goodrive20-EU series VFDs provide 3 channels
analog
input
terminals
as
the
standard
configuration, of which AI1 is adjusting through
analog
potentiometer,
while
AI2
is
the
voltage/current option (0
–10V/0–20mA) which
can be shifted by jumpers; while AI3 is voltage
input (-10V
–+10V).
Note:
When analog AI2 select 0
–20mA input, the
corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds
to the maximum frequency (function code
P00.03) in forward direction and -100.0%
corresponds to the maximum frequency in
reverse direction (function code P00.03)
4: Set via high-speed pulse HDI
The frequency is set by high-speed pulse
terminals. Goodrive20 series VFDs provide 1
high speed pulse input as the standard
configuration. The pulse frequency range is
0.00
–50.00kHz.
0
○
P00.07
B frequency
command
selection
2
○