Goodrive20-EU Series VFD
Function parameters
-50-
Function
code
Name
Description
Default Modify
slip
control the speed steady-state error.
Setting range: 50%
–200%
P03.08
Compensation
coefficient of
vector control
brake slip
100%
○
P03.09
Current loop
proportional
coefficient P
Note
:
The two function codes impact the dynamic
response speed and control accuracy of the
system. Generally, you do not need to
modify the two function codes.
The parameters P03.09 and P03.10 are
applicable only to SVC 0 (P00.00=0).
Setting range: 0
–65535
1000
○
P03.10
Current loop
integral
coefficient I
1000
○
P03.11
Torque setting
mode selection
This parameter is used to enable the torque
control mode, and set the torque setting means.
0: Torque control is invalid
1: Set via keypad
(
P3.12
)
2: Set via AI1 (100% relative to three times of
motor current)
3: Set via AI2 (100% relative to three times of
motor) (same as above)
4: Set via AI3 (100% relative to three times of
motor) (same as above)
5: Set via pulse frequency HDI (same as above)
6: Multi-step torque setting (same as above)
7: Set via Modbus communication
8
–10: Reserved
Note
: Setting mode 2
–7, 100% corresponds to 3
times of the motor rated current
0
○
P03.12
Keypad setting
torque
Setting range: -300.0%
–300.0% (motor rated
current)
50.0%
○
P03.13
Torque
reference filter
time
0.000
–10.000s
0.100s
○
P03.14
Setting source
of upper-limit
frequency of
forward
0: Set via keypad (P03.16 sets P03.14, P03.17
sets P03.15)
1: Set via AI1 (100% corresponds to max.
frequency)
0
○