Goodrive20-EU Series VFD
Function parameters
-51-
Function
code
Name
Description
Default Modify
rotation in
torque control
2: Set via AI2 (same as above)
3: Set via AI3 (same as above)
4: Set via pulse frequency HDI (same as above)
5: Set via multi-step (same as above)
6: Set via Modbus communication (same as
above)
7
–9: Reserved
Note: setting method 1
–9, 100% corresponds to
the maximum frequency
P03.15
Setting source
of upper-limit
frequency of
reverse
rotation in
torque control
0
○
P03.16
Torque control
forward
rotation
upper-limit
frequency
keypad limit
value
This function is used to set the upper limit of the
frequency. P03.16 sets the value of P03.14;
P03.17 sets the value of P03.15.
Setting range: 0.00 Hz
–P00.03 (the max. output
frequency)
50.00
Hz
○
P03.17
Torque control
reverse
rotation
upper-limit
frequency
keypad limit
value
50.00
Hz
○
P03.18
Upper-limit
setting of
electromotion
torque
This function code is used to select the
electromotion and braking torque upper-limit
setting source selection.
0: Set via keypad (P03.20 sets P03.18 and
P03.21 sets P03.19)
1: Set via AI1 (100% relative to three times of
motor current)
2: Set via AI2 (same as above)
3: Set via AI3 (same as above)
4: Set via HDI (same as above)
5: Set via Modbus communication (same as
above)
6
–8: Reserved
Note:
Setting mode 1
–8, 100% corresponds to
three times of the motor current.
0
○
P03.19
Upper-limit
setting of
braking torque
0
○