Goodrive20-EU Series VFD
Installation guidelines
-25-
1: STO trigger delay: Time interval between trigger the STO function and switching off the
drive output.
2: STO indication delay: Time interval between trigger the STO function and STO output state
indication.
3.3.3 STO function installation checklist
Before installing STO, please perform self-inspection according to below table to ensure the
effectiveness of STO.
Item
□
Ensure that the drive can be run and stopped freely during commissioning.
□
Stop the drive (if running), cut off input power and isolate the drive from the power cable
via the switch
□
Check STO circuit connection against circuit diagram.
□
Check that the shield of STO input cable is connected to +24V reference GND COM
□
Power on
□
Test the operation of STO when the motor is stopped:
•
Give a stop command to the drive (if running) and wait until the motor shaft is at
standstill.
•
Activate STO function and give a start command to the drive, ensure the motor stays
at standstill.
•
Inactivate STO circuit.
□
Restart the drive and check if the motor runs normally
□
Test the operation of STO function when the motor is running:
•
Start the drive and ensure the motor runs normally.
•
Activate STO circuit.
•
The drive reports STO fault (refer to fault and countermeasure in page X), ensure that
motor coast to stop and stops rotation.
•
Inactivate STO circuit.
□
Restart the drive and check if the motor runs normally
3.4 Layout protection
3.4.1 Protecting the VFD and input power cable in short-circuit situations
Protect the VFD and input power cable in short circuit situations and against thermal overload.
Arrange the protection according to the following guidelines.
Содержание Goodrive20-EU VFD Series
Страница 1: ......
Страница 173: ...6 6 0 0 1 0 0 4 8 4...