Goodrive20-EU Series VFD
Function parameters
-62-
Function
code
Name
Description
Default Modify
Note
: For the 2-wire running mode, when
FWD/REV terminal is valid, the VFD stop
because of the stopping command from other
sources, even the control terminal FWD/REV
keeps valid; the VFD won't work when the
stopping command is canceled. Only when
FWD/REV is re-launched, the VFD can start
again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop
and terminal control (see P07.04).
P05.14
S1 terminal
switching on
delay time
The function code defines the corresponding
delay time of electrical level of the programmable
terminals from switching on to switching off.
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000
–50.000s
0.000s
○
P05.15
S1 terminal
switching off
delay time
0.000s
○
P05.16
S2 terminal
switching on
delay time
0.000s
○
P05.17
S2 terminal
switching off
delay time
0.000s
○
P05.18
S3 terminal
switching on
delay time
0.000s
○
P05.19
S3 terminal
switching off
delay time
0.000s
○
P05.20
S4 terminal
switching on
delay time
0.000s
○
P05.21
S4 terminal
switching off
delay time
0.000s
○
P05.30
HDI terminal
switching on
delay time
0.000s
○