Goodrive20-EU Series VFD
Function parameters
-54-
Function
code
Name
Description
Default Modify
Output voltage
Output frequency
Linear type
Square type
Torque step-down V/F curve (1.3 order)
Torque step-down V/F curve (1.7 order)
Torque step-down V/F curve (2.0 order)
P04.01 Torque boost
Torque boost to the output voltage for the
features of low frequency torque. P04.01 is for
the max. output voltage V
b
.
P04.02 defines the percentage of closing
frequency of manual torque to f
b
.
Torque boost should be selected according to
the load. The bigger the load is, the bigger the
torque is. Too big torque boost is inappropriate
because the motor will run with over magnetic,
and the current of the VFD will increase to add
the temperature of the VFD and decrease the
efficiency.
When the torque boost is set to 0.0%, the VFD is
automatic torque boost.
Torque boost threshold: below this frequency
point, the torque boost is valid, but over this
frequency point, the torque boost is invalid.
Output voltage
Output
frequency
Cut-off
boost
b
f
f
v
v
Setting range of P04.01: 0.0%: (automatic)
0.1%
–10.0%
Setting range of P04.02: 0.0%
–50.0%
0.0%
○
P04.02
Torque boost
end
20.0%
○
P04.03
V/F frequency
point 1
Output voltage
Output
frequency
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
0.00Hz
○
P04.04
V/F voltage
point 1
0.0%
○
P04.05
V/F frequency
point 2
0.00Hz
○