P14.01
Communication
baud rate
setup
Set the digital transmission speed between the
upper monitor and the VFD.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
Note:
The baud rate between the upper monitor
and the VFD must be the same. Otherwise, the
communication is not applied. The bigger the
baud rate, the quicker the communication speed.
4
○
P14.02
Data bit check
setup
The data format between the upper monitor and
the VFD must be the same. Otherwise, the
communication is not applied.
0: No parity check (N, 8, 1) for RTU
1: Even parity check (E, 8, 1) for RTU
2: Odd parity check (O, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even parity check (E, 8, 2) for RTU
5: Odd parity check (O, 8, 2) for RTU
6: No check (N, 7, 1) for ASCII
7: Even check (E, 7, 1) for ASCII
8: Odd check (O, 7, 1) for ASCII
9: No check (N, 7, 2) for ASCII
10: Even check (E, 7, 2) for ASCII
11: Odd check (O, 7, 2) for ASCII
12: No check (N, 8, 1) for ASCII
13: Even check (E, 8, 1) for ASCII
14: Odd check (O, 8, 1) for ASCII
15: No check (N, 8, 2) for ASCII
16: Even check (E, 8, 2) for ASCII
17: Odd check (O, 8, 2) for ASCII
1
○
P14.03
Communication
response delay
0
–200ms
It means the interval time between the drive
receive the data and sent it to the upper monitor.
If the answer delay is shorter than the system
processing time, then the answer delay time is
5
○