Goodrive20-EU Series VFD
Optional peripheral accessories
-159-
C.6.2 C3 filter
Goodrive20-EU series 1PH 220V/3PH 380V 2.2kW and below, 3PH 220V 0.75kW and below
models can satisfy the requirements of IEC61800-3 C3 as shown in the table below; 3PH
380V 4kW and above, 3PH 220V 1.5kW and above models can be set to satisfy the
requirements of IEC61800-3 C3 or not by jumper J10.
Note: Disconnect J10 when either of below situations occurs:
1. EMC filter is suitable for the neutral-grounding grid system. If it is used in IT grid system
(neutral point is not grounded), disconnect J10.
2. During configuring residual current circuit-breaker, if tripping occurred during startup,
disconnect J10.
Interference filter on input side: As the VFD may interfere with peripheral devices during
working, this filter can be used to reduce the interference.
Noise filter on output side: This filter can be used to reduce the radio noise caused between
the VFD and motor as well as the leakage current of the lead wires.
Model
Input filter
GD20-0R4G-S2-EU
FLT-PS2004L-C-G
GD20-0R7G-S2-EU
GD20-1R5G-S2-EU
GD20-2R2G-S2-EU
GD20-0R4G-2-EU
FLT-P04008L-C-G
GD20-0R7G-2-EU
GD20-0R7G-4-EU
GD20-1R5G-4-EU
GD20-2R2G-4-EU
Note:
The input EMI meet the requirement of C3 after adding input filters.
Above options are external, the customer should indicate when purchasing.