Goodrive20-EU Series VFD
Function parameters
-97-
Function
code
Name
Description
Default Modify
the system processing time, if the answer delay
is longer than the system processing time, then
after the system deal with the data, waits until
achieving the answer delay time to send the data
to the upper monitor.
P14.04
Communication
overtime fault
time
0.0 (invalid), 0.1
–60.0s
When the function code is set as 0.0, the
communication overtime parameter is invalid.
When the function code is set as non-zero, if the
interval time between two communications
exceeds the communication overtime, the
system will report "485 communication faults"
(CE).
0.0s
○
P14.05
Transmission
error
processing
0: Alarm and stop freely
1: No alarm and continue running
2: No alarm and stop as per the stop mode (only
under communication control mode)
3: No alarm and stop as per the stop mode
(under all control modes)
0
○
P14.06
Communication
processing
action selection
0x000
–0x111
Ones place: Responding to write operations
0: Yes
1: No
Tens place: Communication encryption
0: Disabled
1: Enabled
Hundreds place: User-defined communication
command address
0: Disabled
1: Enabled
0x000
○
P14.07
User-defined
address for
running
commands
0x0000
–0xffff
0x1000
○
P14.08
User-defined
address for
frequency
setting
0x0000
–0xffff
0x2000
○