Goodrive20-EU Series VFD
Function parameters
-91-
Function
code
Name
Description
Default Modify
1: Minutes; the running time of all stages is
counted by minute
P11 group Protection parameters
Function
code
Name
Description
Default Modify
P11.00
Phase loss
protection
0x00
–0x11
Ones place:
0: Input phase loss software protection disable
1: Input phase loss software protection enable
Tens place:
0: Output phase loss protection disable
1: Output phase loss protection enable
Hundreds place:
0: Input phase loss hardware protection disable
1: Input phase loss hardware protection enable
0x10
○
P11.01
Frequency-
drop at sudden
power dip
0: Disable
1: Enable
0
○
P11.02
Frequency-
drop ratio at
sudden power
dip
Setting range: 0.00Hz/s
–P00.03 (the max.
frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point,
the VFD begin to decrease the running
frequency at P11.02, to make the VFD generate
power again. The returning power can maintain
the bus voltage to ensure a rated running of the
VFD until the recovery of power.
Voltage
degree
220/
230V
400V
460V
660V
Frequency
decrease
point at
sudden
power loss
240V 460V
530V
800V
Note:
Adjust the parameter properly to avoid the
stopping caused by VFD protection during the
10.00
Hz/s
○