Goodrive20-EU Series VFD
Function parameters
-55-
Function
code
Name
Description
Default Modify
P04.06
V/F voltage
point 2
When P04.00 =1, the user can set V//F curve
through P04.03
–P04.08.
V/F is generally set according to the load of the
motor.
Note:
V1<V2<V3, f1<f2<f3. Too high low
frequency voltage will heat the motor excessively
or damage. Overcurrent stall or overcurrent
protection may occur.
Setting range of P04.03: 0.00Hz
–P04.05
Setting range of P04.04, P04.06 and P04.08:
0.0%
–110.0% (rated motor voltage)
Setting range of P04.05: P04.03
–P04.07
Setting range of P04.07: P04.05
–P02.02 (rated
motor voltage frequency)
0.0%
○
P04.07
V/F frequency
point 3
0.00Hz
○
P04.08
V/F voltage
point 3
0.0%
○
P04.09
V/F slip
compensation
gain
This function code is used to compensate the
change of the rotation speed caused by load
during compensation SVPWM control to improve
the rigidity of the motor. It can be set to the rated
slip frequency of the motor which is counted as
below:
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor,
its function code is P02.02; n is the rated rotating
speed of the motor and its function code is
P02.03; p is the pole pair of the motor. 100.0%
corresponds to the rated slip frequency
△
f.
Setting range: 0.0
–200.0%
100.0%
○
P04.10
Low frequency
vibration
control factor
In the SVPWM control mode, current fluctuation
may occur to the motor on some frequency,
especially the motor with big power. The motor
cannot run stably or overcurrent may occur.
These phenomena can be canceled by adjusting
this parameter.
Setting range of P04.10: 0
–100
Setting range of P04.11: 0
–100
Setting range of P04.12: 0.00Hz
–P00.03 (the
max. frequency)
10
○
P04.11
High frequency
vibration
control factor
10
○
P04.12
Vibration
control
threshold
30.00
Hz
○