Goodrive20-EU Series VFD
Function parameters
-93-
Function
code
Name
Description
Default Modify
0: current limit invalid
1: current limit valid
2: current limit is invalid during constant speed
Setting range of P11.05: 0x00
–0x12
Setting range of P11.06: 50.0
–200.0% (relative
to the percentage of rated current of the VFD)
Setting range of P11.07: 0.00
–50.00Hz/s
P11.08
Over/under-
load pre-alarm
of motor/ VFD
The output current of the VFD or the motor is
above P11.09 and the lasting time is beyond
P11.10, overload pre-alarm will be output.
Output current
Overload
pre-warning
point
T
T
Y,
RO1, RO2
Pre-warning
time
Pre-warning
time
Setting range of P11.08:
Enable and define the overload pre-alarm of the
VFD or the motor.
Setting range: 0x000
–0x132
Ones place:
0: Motor overload/underload pre-alarm, relative
to rated motor current;
1: VFD overload/underload pre-alarm, relative to
rated VFD current.
2: Motor output torque overload/underload
pre-alarm, relative to rated motor torque
Tens place:
0:
The
VFD
continues
to
work
after
over/under-load pre-alarm
1: The VFD continues to work after underload
pre-alarm and stops running after overload fault
2: The VFD continues to work after overload
pre-alarm and stops running after underload fault
0x000
○
P11.09
Overload
pre-alarm
detection level
150%
○
P11.10
Overload
pre-alarm
detection time
1.0s
○
Содержание Goodrive20-EU VFD Series
Страница 1: ......
Страница 173: ...6 6 0 0 1 0 0 4 8 4...